Kabelarea för 425 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 25 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.52V (0.66%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.88V (0.82%)
Voltage at Load228.5 VLine Loss: 644.2 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A303.17 V (131.81%)0.0 V500.08 V (217.43%)128845.8 WDrop High
2.5 mm²24 A18 A181.9 V (79.09%)48.1 V300.05 V (130.46%)77307.5 WDrop High
4 mm²32 A25 A113.69 V (49.43%)116.3 V187.53 V (81.54%)48317.2 WDrop High
6 mm²41 A32 A75.79 V (32.95%)154.2 V125.02 V (54.36%)32211.5 WDrop High
10 mm²57 A44 A45.47 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
16 mm²76 A59 A28.42 V (12.36%)201.6 V46.88 V (20.38%)12079.3 WDrop High
25 mm²101 A78 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.7 WDrop High
35 mm²125 A97 A12.99 V (5.65%)217.0 V21.43 V (9.32%)5522.0 WDrop High
50 mm²151 A118 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 WDrop High
70 mm²192 A150 A6.5 V (2.82%)223.5 V10.72 V (4.66%)2761.0 WDrop High
95 mm²232 A181 A4.79 V (2.08%)225.2 V7.9 V (3.43%)2034.4 WDrop High
120 mm²269 A210 A3.79 V (1.65%)226.2 V6.25 V (2.72%)1610.6 WDrop High
150 mm²309 A241 A3.03 V (1.32%)227.0 V5.0 V (2.17%)1288.5 WDrop High
185 mm²353 A275 A2.46 V (1.07%)227.5 V4.05 V (1.76%)1044.7 WDrop High
240 mm²415 A324 A1.89 V (0.82%)228.1 V3.13 V (1.36%)805.3 WDrop High
300 mm²477 A372 A1.52 V (0.66%)228.5 V2.5 V (1.09%)644.2 W✓ OK (≤3%)
400 mm²570 A445 A1.14 V (0.49%)228.9 V1.88 V (0.82%)483.2 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 425A vid 25 meter (230V)?

För 425 Ampere över 25 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.52V / 0.66%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.