Kabelarea för 425 Ampere vid 40 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 40 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.43V (1.05%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.0V (1.3%)
Voltage at Load227.6 VLine Loss: 1030.8 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A485.07 V (210.9%)0.0 V800.13 V (347.88%)206153.3 WDrop High
2.5 mm²24 A18 A291.04 V (126.54%)0.0 V480.08 V (208.73%)123692.0 WDrop High
4 mm²32 A25 A181.9 V (79.09%)48.1 V300.05 V (130.46%)77307.5 WDrop High
6 mm²41 A32 A121.27 V (52.72%)108.7 V200.03 V (86.97%)51538.3 WDrop High
10 mm²57 A44 A72.76 V (31.63%)157.2 V120.02 V (52.18%)30923.0 WDrop High
16 mm²76 A59 A45.48 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
25 mm²101 A78 A29.1 V (12.65%)200.9 V48.01 V (20.87%)12369.2 WDrop High
35 mm²125 A97 A20.79 V (9.04%)209.2 V34.29 V (14.91%)8835.1 WDrop High
50 mm²151 A118 A14.55 V (6.33%)215.4 V24.0 V (10.44%)6184.6 WDrop High
70 mm²192 A150 A10.39 V (4.52%)219.6 V17.15 V (7.45%)4417.6 WDrop High
95 mm²232 A181 A7.66 V (3.33%)222.3 V12.63 V (5.49%)3255.1 WDrop High
120 mm²269 A210 A6.06 V (2.64%)223.9 V10.0 V (4.35%)2576.9 WDrop High
150 mm²309 A241 A4.85 V (2.11%)225.1 V8.0 V (3.48%)2061.5 WDrop High
185 mm²353 A275 A3.93 V (1.71%)226.1 V6.49 V (2.82%)1671.5 WDrop High
240 mm²415 A324 A3.03 V (1.32%)227.0 V5.0 V (2.17%)1288.5 WDrop High
300 mm²477 A372 A2.43 V (1.05%)227.6 V4.0 V (1.74%)1030.8 W✓ OK (≤3%)
400 mm²570 A445 A1.82 V (0.79%)228.2 V3.0 V (1.3%)773.1 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 40 Meter (230V)

Vilken kabelarea krävs för 425A vid 40 meter (230V)?

För 425 Ampere över 40 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.43V / 1.05%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.