Kabelarea för 425 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 30 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.82V (0.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.25V (0.98%)
Voltage at Load228.2 VLine Loss: 773.1 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A363.8 V (158.17%)0.0 V600.1 V (260.91%)154615.0 WDrop High
2.5 mm²24 A18 A218.28 V (94.9%)11.7 V360.06 V (156.55%)92769.0 WDrop High
4 mm²32 A25 A136.43 V (59.32%)93.6 V225.04 V (97.84%)57980.6 WDrop High
6 mm²41 A32 A90.95 V (39.54%)139.1 V150.03 V (65.23%)38653.8 WDrop High
10 mm²57 A44 A54.57 V (23.73%)175.4 V90.02 V (39.14%)23192.3 WDrop High
16 mm²76 A59 A34.11 V (14.83%)195.9 V56.26 V (24.46%)14495.2 WDrop High
25 mm²101 A78 A21.83 V (9.49%)208.2 V36.01 V (15.65%)9276.9 WDrop High
35 mm²125 A97 A15.59 V (6.78%)214.4 V25.72 V (11.18%)6626.4 WDrop High
50 mm²151 A118 A10.91 V (4.75%)219.1 V18.0 V (7.83%)4638.4 WDrop High
70 mm²192 A150 A7.8 V (3.39%)222.2 V12.86 V (5.59%)3313.2 WDrop High
95 mm²232 A181 A5.74 V (2.5%)224.3 V9.48 V (4.12%)2441.3 WDrop High
120 mm²269 A210 A4.55 V (1.98%)225.5 V7.5 V (3.26%)1932.7 WDrop High
150 mm²309 A241 A3.64 V (1.58%)226.4 V6.0 V (2.61%)1546.2 WDrop High
185 mm²353 A275 A2.95 V (1.28%)227.1 V4.87 V (2.12%)1253.6 WDrop High
240 mm²415 A324 A2.27 V (0.99%)227.7 V3.75 V (1.63%)966.3 WDrop High
300 mm²477 A372 A1.82 V (0.79%)228.2 V3.0 V (1.3%)773.1 W✓ OK (≤3%)
400 mm²570 A445 A1.36 V (0.59%)228.6 V2.25 V (0.98%)579.8 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 425A vid 30 meter (230V)?

För 425 Ampere över 30 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.82V / 0.79%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.