Kabelarea för 425 Ampere vid 150 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 150 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.82V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.25V (4.89%)
Voltage at Load223.2 VLine Loss: 2899.0 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1819.0 V (790.87%)0.0 V3000.5 V (1304.57%)773075.0 WDrop High
2.5 mm²24 A18 A1091.4 V (474.52%)0.0 V1800.3 V (782.74%)463845.0 WDrop High
4 mm²32 A25 A682.12 V (296.58%)0.0 V1125.19 V (489.21%)289903.1 WDrop High
6 mm²41 A32 A454.75 V (197.72%)0.0 V750.12 V (326.14%)193268.8 WDrop High
10 mm²57 A44 A272.85 V (118.63%)0.0 V450.07 V (195.68%)115961.2 WDrop High
16 mm²76 A59 A170.53 V (74.14%)59.5 V281.3 V (122.3%)72475.8 WDrop High
25 mm²101 A78 A109.14 V (47.45%)120.9 V180.03 V (78.27%)46384.5 WDrop High
35 mm²125 A97 A77.96 V (33.89%)152.0 V128.59 V (55.91%)33131.8 WDrop High
50 mm²151 A118 A54.57 V (23.73%)175.4 V90.02 V (39.14%)23192.2 WDrop High
70 mm²192 A150 A38.98 V (16.95%)191.0 V64.3 V (27.95%)16565.9 WDrop High
95 mm²232 A181 A28.72 V (12.49%)201.3 V47.38 V (20.6%)12206.4 WDrop High
120 mm²269 A210 A22.74 V (9.89%)207.3 V37.51 V (16.31%)9663.4 WDrop High
150 mm²309 A241 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.8 WDrop High
185 mm²353 A275 A14.75 V (6.41%)215.3 V24.33 V (10.58%)6268.2 WDrop High
240 mm²415 A324 A11.37 V (4.94%)218.6 V18.75 V (8.15%)4831.7 WDrop High
300 mm²477 A372 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 W~ ≤5%
400 mm²570 A445 A6.82 V (2.97%)223.2 V11.25 V (4.89%)2899.0 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 150 Meter (230V)

Vilken kabelarea krävs för 425A vid 150 meter (230V)?

För 425 Ampere över 150 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.82V / 2.97%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.