Kabelarea för 45 Ampere vid 5 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 5 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 0.83V (0.21%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.86V (0.21%)
Voltage at Load399.2 VLine Loss: 65.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.56 V (1.39%)394.4 V9.17 V (2.29%)433.3 WDrop High
2.5 mm²24 A18 A3.34 V (0.83%)396.7 V5.5 V (1.38%)260.0 WDrop High
4 mm²32 A25 A2.08 V (0.52%)397.9 V3.44 V (0.86%)162.5 WDrop High
6 mm²41 A32 A1.39 V (0.35%)398.6 V2.29 V (0.57%)108.3 WDrop High
10 mm²57 A44 A0.83 V (0.21%)399.2 V1.38 V (0.34%)65.0 W✓ OK (≤3%)
16 mm²76 A59 A0.52 V (0.13%)399.5 V0.86 V (0.21%)40.6 W✓ OK (≤3%)
25 mm²101 A78 A0.33 V (0.08%)399.7 V0.55 V (0.14%)26.0 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (0.06%)399.8 V0.39 V (0.1%)18.6 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.04%)399.8 V0.28 V (0.07%)13.0 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.03%)399.9 V0.2 V (0.05%)9.3 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.02%)399.9 V0.14 V (0.04%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.02%)399.9 V0.11 V (0.03%)5.4 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)399.9 V0.09 V (0.02%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)400.0 V0.07 V (0.02%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)400.0 V0.06 V (0.01%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)400.0 V0.05 V (0.01%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)400.0 V0.03 V (0.01%)1.6 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 5 Meter (400V)

Vilken kabelarea krävs för 45A vid 5 meter (400V)?

För 45 Ampere över 5 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (0.83V / 0.21%).

Hur stor effekt motsvarar 45A vid 400V?

Det motsvarar 31.18 kW med en rekommenderad säkring på 45A.