Kabelarea för 45 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 35 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.84V (1.46%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 6.02V (1.5%)
Voltage at Load394.2 VLine Loss: 455.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.92 V (9.73%)361.1 V64.2 V (16.05%)3033.5 WDrop High
2.5 mm²24 A18 A23.35 V (5.84%)376.6 V38.52 V (9.63%)1820.1 WDrop High
4 mm²32 A25 A14.59 V (3.65%)385.4 V24.07 V (6.02%)1137.5 WDrop High
6 mm²41 A32 A9.73 V (2.43%)390.3 V16.05 V (4.01%)758.4 WDrop High
10 mm²57 A44 A5.84 V (1.46%)394.2 V9.63 V (2.41%)455.0 W✓ OK (≤3%)
16 mm²76 A59 A3.65 V (0.91%)396.4 V6.02 V (1.5%)284.4 W✓ OK (≤3%)
25 mm²101 A78 A2.34 V (0.58%)397.7 V3.85 V (0.96%)182.0 W✓ OK (≤3%)
35 mm²125 A97 A1.67 V (0.42%)398.3 V2.75 V (0.69%)130.0 W✓ OK (≤3%)
50 mm²151 A118 A1.17 V (0.29%)398.8 V1.93 V (0.48%)91.0 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.21%)399.2 V1.38 V (0.34%)65.0 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.15%)399.4 V1.01 V (0.25%)47.9 W✓ OK (≤3%)
120 mm²269 A210 A0.49 V (0.12%)399.5 V0.8 V (0.2%)37.9 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.1%)399.6 V0.64 V (0.16%)30.3 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.08%)399.7 V0.52 V (0.13%)24.6 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.06%)399.8 V0.4 V (0.1%)19.0 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.32 V (0.08%)15.2 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)399.9 V0.24 V (0.06%)11.4 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 45A vid 35 meter (400V)?

För 45 Ampere över 35 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.84V / 1.46%).

Hur stor effekt motsvarar 45A vid 400V?

Det motsvarar 31.18 kW med en rekommenderad säkring på 45A.