Kabelarea för 45 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 30 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.0V (1.25%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.16V (1.29%)
Voltage at Load395.0 VLine Loss: 390.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A33.36 V (8.34%)366.6 V55.03 V (13.76%)2600.1 WDrop High
2.5 mm²24 A18 A20.02 V (5.0%)380.0 V33.02 V (8.25%)1560.1 WDrop High
4 mm²32 A25 A12.51 V (3.13%)387.5 V20.64 V (5.16%)975.0 WDrop High
6 mm²41 A32 A8.34 V (2.08%)391.7 V13.76 V (3.44%)650.0 WDrop High
10 mm²57 A44 A5.0 V (1.25%)395.0 V8.25 V (2.06%)390.0 W✓ OK (≤3%)
16 mm²76 A59 A3.13 V (0.78%)396.9 V5.16 V (1.29%)243.8 W✓ OK (≤3%)
25 mm²101 A78 A2.0 V (0.5%)398.0 V3.3 V (0.83%)156.0 W✓ OK (≤3%)
35 mm²125 A97 A1.43 V (0.36%)398.6 V2.36 V (0.59%)111.4 W✓ OK (≤3%)
50 mm²151 A118 A1.0 V (0.25%)399.0 V1.65 V (0.41%)78.0 W✓ OK (≤3%)
70 mm²192 A150 A0.71 V (0.18%)399.3 V1.18 V (0.29%)55.7 W✓ OK (≤3%)
95 mm²232 A181 A0.53 V (0.13%)399.5 V0.87 V (0.22%)41.1 W✓ OK (≤3%)
120 mm²269 A210 A0.42 V (0.1%)399.6 V0.69 V (0.17%)32.5 W✓ OK (≤3%)
150 mm²309 A241 A0.33 V (0.08%)399.7 V0.55 V (0.14%)26.0 W✓ OK (≤3%)
185 mm²353 A275 A0.27 V (0.07%)399.7 V0.45 V (0.11%)21.1 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.05%)399.8 V0.34 V (0.09%)16.3 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)399.8 V0.28 V (0.07%)13.0 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.21 V (0.05%)9.8 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 45A vid 30 meter (400V)?

För 45 Ampere över 30 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.0V / 1.25%).

Hur stor effekt motsvarar 45A vid 400V?

Det motsvarar 31.18 kW med en rekommenderad säkring på 45A.