Kabelarea för 45 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 15 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 2.5V (0.63%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 2.58V (0.64%)
Voltage at Load397.5 VLine Loss: 195.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A16.68 V (4.17%)383.3 V27.51 V (6.88%)1300.0 WDrop High
2.5 mm²24 A18 A10.01 V (2.5%)390.0 V16.51 V (4.13%)780.0 WDrop High
4 mm²32 A25 A6.25 V (1.56%)393.7 V10.32 V (2.58%)487.5 WDrop High
6 mm²41 A32 A4.17 V (1.04%)395.8 V6.88 V (1.72%)325.0 WDrop High
10 mm²57 A44 A2.5 V (0.63%)397.5 V4.13 V (1.03%)195.0 W✓ OK (≤3%)
16 mm²76 A59 A1.56 V (0.39%)398.4 V2.58 V (0.64%)121.9 W✓ OK (≤3%)
25 mm²101 A78 A1.0 V (0.25%)399.0 V1.65 V (0.41%)78.0 W✓ OK (≤3%)
35 mm²125 A97 A0.71 V (0.18%)399.3 V1.18 V (0.29%)55.7 W✓ OK (≤3%)
50 mm²151 A118 A0.5 V (0.13%)399.5 V0.83 V (0.21%)39.0 W✓ OK (≤3%)
70 mm²192 A150 A0.36 V (0.09%)399.6 V0.59 V (0.15%)27.9 W✓ OK (≤3%)
95 mm²232 A181 A0.26 V (0.07%)399.7 V0.43 V (0.11%)20.5 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.05%)399.8 V0.34 V (0.09%)16.3 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.04%)399.8 V0.28 V (0.07%)13.0 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.03%)399.9 V0.22 V (0.06%)10.5 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.03%)399.9 V0.17 V (0.04%)8.1 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)399.9 V0.14 V (0.03%)6.5 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)399.9 V0.1 V (0.03%)4.9 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 45A vid 15 meter (400V)?

För 45 Ampere över 15 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (2.5V / 0.63%).

Hur stor effekt motsvarar 45A vid 400V?

Det motsvarar 31.18 kW med en rekommenderad säkring på 45A.