⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 450 Ampere vid 20 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 20 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.11V (0.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.38V (0.34%)
Voltage at Load398.9 VLine Loss: 866.7 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (55.6%)177.6 V366.85 V (91.71%)173340.0 WDrop High
2.5 mm²24 A18 A133.44 V (33.36%)266.6 V220.11 V (55.03%)104004.0 WDrop High
4 mm²32 A25 A83.4 V (20.85%)316.6 V137.57 V (34.39%)65002.5 WDrop High
6 mm²41 A32 A55.6 V (13.9%)344.4 V91.71 V (22.93%)43335.0 WDrop High
10 mm²57 A44 A33.36 V (8.34%)366.6 V55.03 V (13.76%)26001.0 WDrop High
16 mm²76 A59 A20.85 V (5.21%)379.2 V34.39 V (8.6%)16250.6 WDrop High
25 mm²101 A78 A13.34 V (3.34%)386.7 V22.01 V (5.5%)10400.4 WDrop High
35 mm²125 A97 A9.53 V (2.38%)390.5 V15.72 V (3.93%)7428.9 WDrop High
50 mm²151 A118 A6.67 V (1.67%)393.3 V11.01 V (2.75%)5200.2 WDrop High
70 mm²192 A150 A4.77 V (1.19%)395.2 V7.86 V (1.97%)3714.4 WDrop High
95 mm²232 A181 A3.51 V (0.88%)396.5 V5.79 V (1.45%)2736.9 WDrop High
120 mm²269 A210 A2.78 V (0.69%)397.2 V4.59 V (1.15%)2166.8 WDrop High
150 mm²309 A241 A2.22 V (0.56%)397.8 V3.67 V (0.92%)1733.4 WDrop High
185 mm²353 A275 A1.8 V (0.45%)398.2 V2.97 V (0.74%)1405.5 WDrop High
240 mm²415 A324 A1.39 V (0.35%)398.6 V2.29 V (0.57%)1083.4 WDrop High
300 mm²477 A372 A1.11 V (0.28%)398.9 V1.83 V (0.46%)866.7 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.21%)399.2 V1.38 V (0.34%)650.0 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 20 Meter (400V)

Vilken kabelarea krävs för 450A vid 20 meter (400V)?

För 450 Ampere över 20 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.11V / 0.28%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.