Kabelarea för 450 Ampere vid 35 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 35 m vid 400V.
Copper Cable (≤3% Drop)300 mm²Drop: 1.95V (0.49%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.41V (0.6%)
Voltage at Load398.1 VLine Loss: 1516.7 W
Max Power & Breaker311.77 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 389.19 V (97.3%) | 10.8 V | 641.98 V (160.5%) | 303345.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 233.52 V (58.38%) | 166.5 V | 385.19 V (96.3%) | 182007.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 145.95 V (36.49%) | 254.1 V | 240.74 V (60.19%) | 113754.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 97.3 V (24.32%) | 302.7 V | 160.5 V (40.12%) | 75836.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 58.38 V (14.59%) | 341.6 V | 96.3 V (24.07%) | 45501.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 36.49 V (9.12%) | 363.5 V | 60.19 V (15.05%) | 28438.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 23.35 V (5.84%) | 376.6 V | 38.52 V (9.63%) | 18200.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 13000.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 11.68 V (2.92%) | 388.3 V | 19.26 V (4.81%) | 9100.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 6500.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 6.15 V (1.54%) | 393.9 V | 10.14 V (2.53%) | 4789.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 4.86 V (1.22%) | 395.1 V | 8.02 V (2.01%) | 3791.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 3.89 V (0.97%) | 396.1 V | 6.42 V (1.6%) | 3033.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.16 V (0.79%) | 396.8 V | 5.21 V (1.3%) | 2459.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.43 V (0.61%) | 397.6 V | 4.01 V (1.0%) | 1895.9 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.95 V (0.49%) | 398.1 V | 3.21 V (0.8%) | 1516.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.46 V (0.36%) | 398.5 V | 2.41 V (0.6%) | 1137.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 450 Ampere vid 35 Meter (400V)
Vilken kabelarea krävs för 450A vid 35 meter (400V)?
För 450 Ampere över 35 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.95V / 0.49%).
Hur stor effekt motsvarar 450A vid 400V?
Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.
Related Lengths & Currents (400V)
450A · 5m (400V)450A · 10m (400V)450A · 15m (400V)450A · 20m (400V)450A · 25m (400V)450A · 30m (400V)450A · 40m (400V)450A · 45m (400V)450A · 50m (400V)450A · 60m (400V)450A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)