Kabelarea för 450 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 35 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.95V (0.49%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.41V (0.6%)
Voltage at Load398.1 VLine Loss: 1516.7 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A389.19 V (97.3%)10.8 V641.98 V (160.5%)303345.0 WDrop High
2.5 mm²24 A18 A233.52 V (58.38%)166.5 V385.19 V (96.3%)182007.0 WDrop High
4 mm²32 A25 A145.95 V (36.49%)254.1 V240.74 V (60.19%)113754.4 WDrop High
6 mm²41 A32 A97.3 V (24.32%)302.7 V160.5 V (40.12%)75836.2 WDrop High
10 mm²57 A44 A58.38 V (14.59%)341.6 V96.3 V (24.07%)45501.8 WDrop High
16 mm²76 A59 A36.49 V (9.12%)363.5 V60.19 V (15.05%)28438.6 WDrop High
25 mm²101 A78 A23.35 V (5.84%)376.6 V38.52 V (9.63%)18200.7 WDrop High
35 mm²125 A97 A16.68 V (4.17%)383.3 V27.51 V (6.88%)13000.5 WDrop High
50 mm²151 A118 A11.68 V (2.92%)388.3 V19.26 V (4.81%)9100.4 WDrop High
70 mm²192 A150 A8.34 V (2.08%)391.7 V13.76 V (3.44%)6500.2 WDrop High
95 mm²232 A181 A6.15 V (1.54%)393.9 V10.14 V (2.53%)4789.7 WDrop High
120 mm²269 A210 A4.86 V (1.22%)395.1 V8.02 V (2.01%)3791.8 WDrop High
150 mm²309 A241 A3.89 V (0.97%)396.1 V6.42 V (1.6%)3033.4 WDrop High
185 mm²353 A275 A3.16 V (0.79%)396.8 V5.21 V (1.3%)2459.6 WDrop High
240 mm²415 A324 A2.43 V (0.61%)397.6 V4.01 V (1.0%)1895.9 WDrop High
300 mm²477 A372 A1.95 V (0.49%)398.1 V3.21 V (0.8%)1516.7 W✓ OK (≤3%)
400 mm²570 A445 A1.46 V (0.36%)398.5 V2.41 V (0.6%)1137.5 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 450A vid 35 meter (400V)?

För 450 Ampere över 35 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.95V / 0.49%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.