Kabelarea för 450 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 10 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 0.56V (0.14%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.69V (0.17%)
Voltage at Load399.4 VLine Loss: 433.3 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A111.2 V (27.8%)288.8 V183.42 V (45.86%)86670.0 WDrop High
2.5 mm²24 A18 A66.72 V (16.68%)333.3 V110.05 V (27.51%)52002.0 WDrop High
4 mm²32 A25 A41.7 V (10.42%)358.3 V68.78 V (17.2%)32501.2 WDrop High
6 mm²41 A32 A27.8 V (6.95%)372.2 V45.86 V (11.46%)21667.5 WDrop High
10 mm²57 A44 A16.68 V (4.17%)383.3 V27.51 V (6.88%)13000.5 WDrop High
16 mm²76 A59 A10.42 V (2.61%)389.6 V17.2 V (4.3%)8125.3 WDrop High
25 mm²101 A78 A6.67 V (1.67%)393.3 V11.01 V (2.75%)5200.2 WDrop High
35 mm²125 A97 A4.77 V (1.19%)395.2 V7.86 V (1.97%)3714.4 WDrop High
50 mm²151 A118 A3.34 V (0.83%)396.7 V5.5 V (1.38%)2600.1 WDrop High
70 mm²192 A150 A2.38 V (0.6%)397.6 V3.93 V (0.98%)1857.2 WDrop High
95 mm²232 A181 A1.76 V (0.44%)398.2 V2.9 V (0.72%)1368.5 WDrop High
120 mm²269 A210 A1.39 V (0.35%)398.6 V2.29 V (0.57%)1083.4 WDrop High
150 mm²309 A241 A1.11 V (0.28%)398.9 V1.83 V (0.46%)866.7 WDrop High
185 mm²353 A275 A0.9 V (0.23%)399.1 V1.49 V (0.37%)702.7 WDrop High
240 mm²415 A324 A0.69 V (0.17%)399.3 V1.15 V (0.29%)541.7 WDrop High
300 mm²477 A372 A0.56 V (0.14%)399.4 V0.92 V (0.23%)433.3 W✓ OK (≤3%)
400 mm²570 A445 A0.42 V (0.1%)399.6 V0.69 V (0.17%)325.0 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 450A vid 10 meter (400V)?

För 450 Ampere över 10 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (0.56V / 0.14%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.