Kabelarea för 450 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 45 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.5V (0.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.1V (0.77%)
Voltage at Load397.5 VLine Loss: 1950.1 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A500.39 V (125.1%)0.0 V825.41 V (206.35%)390015.0 WDrop High
2.5 mm²24 A18 A300.23 V (75.06%)99.8 V495.25 V (123.81%)234009.0 WDrop High
4 mm²32 A25 A187.65 V (46.91%)212.4 V309.53 V (77.38%)146255.6 WDrop High
6 mm²41 A32 A125.1 V (31.27%)274.9 V206.35 V (51.59%)97503.8 WDrop High
10 mm²57 A44 A75.06 V (18.76%)324.9 V123.81 V (30.95%)58502.2 WDrop High
16 mm²76 A59 A46.91 V (11.73%)353.1 V77.38 V (19.35%)36563.9 WDrop High
25 mm²101 A78 A30.02 V (7.51%)370.0 V49.52 V (12.38%)23400.9 WDrop High
35 mm²125 A97 A21.45 V (5.36%)378.6 V35.37 V (8.84%)16714.9 WDrop High
50 mm²151 A118 A15.01 V (3.75%)385.0 V24.76 V (6.19%)11700.4 WDrop High
70 mm²192 A150 A10.72 V (2.68%)389.3 V17.69 V (4.42%)8357.5 WDrop High
95 mm²232 A181 A7.9 V (1.98%)392.1 V13.03 V (3.26%)6158.1 WDrop High
120 mm²269 A210 A6.25 V (1.56%)393.7 V10.32 V (2.58%)4875.2 WDrop High
150 mm²309 A241 A5.0 V (1.25%)395.0 V8.25 V (2.06%)3900.1 WDrop High
185 mm²353 A275 A4.06 V (1.01%)395.9 V6.69 V (1.67%)3162.3 WDrop High
240 mm²415 A324 A3.13 V (0.78%)396.9 V5.16 V (1.29%)2437.6 WDrop High
300 mm²477 A372 A2.5 V (0.63%)397.5 V4.13 V (1.03%)1950.1 W✓ OK (≤3%)
400 mm²570 A445 A1.88 V (0.47%)398.1 V3.1 V (0.77%)1462.6 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 450A vid 45 meter (400V)?

För 450 Ampere över 45 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.5V / 0.63%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.