⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 450 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 80 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.35V (2.76%)
Voltage at Load224.9 VLine Loss: 2311.2 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)462240.0 WDrop High
2.5 mm²24 A18 A616.32 V (267.97%)0.0 V1016.64 V (442.02%)277344.0 WDrop High
4 mm²32 A25 A385.2 V (167.48%)0.0 V635.4 V (276.26%)173340.0 WDrop High
6 mm²41 A32 A256.8 V (111.65%)0.0 V423.6 V (184.17%)115560.0 WDrop High
10 mm²57 A44 A154.08 V (66.99%)75.9 V254.16 V (110.5%)69336.0 WDrop High
16 mm²76 A59 A96.3 V (41.87%)133.7 V158.85 V (69.07%)43335.0 WDrop High
25 mm²101 A78 A61.63 V (26.8%)168.4 V101.66 V (44.2%)27734.4 WDrop High
35 mm²125 A97 A44.02 V (19.14%)186.0 V72.62 V (31.57%)19810.3 WDrop High
50 mm²151 A118 A30.82 V (13.4%)199.2 V50.83 V (22.1%)13867.2 WDrop High
70 mm²192 A150 A22.01 V (9.57%)208.0 V36.31 V (15.79%)9905.1 WDrop High
95 mm²232 A181 A16.22 V (7.05%)213.8 V26.75 V (11.63%)7298.5 WDrop High
120 mm²269 A210 A12.84 V (5.58%)217.2 V21.18 V (9.21%)5778.0 WDrop High
150 mm²309 A241 A10.27 V (4.47%)219.7 V16.94 V (7.37%)4622.4 WDrop High
185 mm²353 A275 A8.33 V (3.62%)221.7 V13.74 V (5.97%)3747.9 WDrop High
240 mm²415 A324 A6.42 V (2.79%)223.6 V10.59 V (4.6%)2889.0 WDrop High
300 mm²477 A372 A5.14 V (2.23%)224.9 V8.47 V (3.68%)2311.2 W✓ OK (≤3%)
400 mm²570 A445 A3.85 V (1.67%)226.1 V6.35 V (2.76%)1733.4 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 450A vid 80 meter (230V)?

För 450 Ampere över 80 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.14V / 2.23%).

Hur stor effekt motsvarar 450A vid 230V?

Det motsvarar 103.5 kW med en rekommenderad säkring på 450A.