Kabelarea för 475 Ampere vid 100 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 100 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 6.78V (2.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.38V (3.65%)
Voltage at Load223.2 VLine Loss: 3218.9 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1355.33 V (589.28%)0.0 V2235.67 V (972.03%)643783.3 WDrop High
2.5 mm²24 A18 A813.2 V (353.57%)0.0 V1341.4 V (583.22%)386270.0 WDrop High
4 mm²32 A25 A508.25 V (220.98%)0.0 V838.38 V (364.51%)241418.7 WDrop High
6 mm²41 A32 A338.83 V (147.32%)0.0 V558.92 V (243.01%)160945.8 WDrop High
10 mm²57 A44 A203.3 V (88.39%)26.7 V335.35 V (145.8%)96567.5 WDrop High
16 mm²76 A59 A127.06 V (55.24%)102.9 V209.59 V (91.13%)60354.7 WDrop High
25 mm²101 A78 A81.32 V (35.36%)148.7 V134.14 V (58.32%)38627.0 WDrop High
35 mm²125 A97 A58.09 V (25.25%)171.9 V95.81 V (41.66%)27590.7 WDrop High
50 mm²151 A118 A40.66 V (17.68%)189.3 V67.07 V (29.16%)19313.5 WDrop High
70 mm²192 A150 A29.04 V (12.63%)201.0 V47.91 V (20.83%)13795.4 WDrop High
95 mm²232 A181 A21.4 V (9.3%)208.6 V35.3 V (15.35%)10165.0 WDrop High
120 mm²269 A210 A16.94 V (7.37%)213.1 V27.95 V (12.15%)8047.3 WDrop High
150 mm²309 A241 A13.55 V (5.89%)216.4 V22.36 V (9.72%)6437.8 WDrop High
185 mm²353 A275 A10.99 V (4.78%)219.0 V18.13 V (7.88%)5219.9 WDrop High
240 mm²415 A324 A8.47 V (3.68%)221.5 V13.97 V (6.08%)4023.6 WDrop High
300 mm²477 A372 A6.78 V (2.95%)223.2 V11.18 V (4.86%)3218.9 W✓ OK (≤3%)
400 mm²570 A445 A5.08 V (2.21%)224.9 V8.38 V (3.65%)2414.2 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 100 Meter (230V)

Vilken kabelarea krävs för 475A vid 100 meter (230V)?

För 475 Ampere över 100 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (6.78V / 2.95%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.