Kabelarea för 475 Ampere vid 60 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 60 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 4.07V (1.77%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.03V (2.19%)
Voltage at Load225.9 VLine Loss: 1931.3 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A813.2 V (353.57%)0.0 V1341.4 V (583.22%)386270.0 WDrop High
2.5 mm²24 A18 A487.92 V (212.14%)0.0 V804.84 V (349.93%)231762.0 WDrop High
4 mm²32 A25 A304.95 V (132.59%)0.0 V503.02 V (218.71%)144851.2 WDrop High
6 mm²41 A32 A203.3 V (88.39%)26.7 V335.35 V (145.8%)96567.5 WDrop High
10 mm²57 A44 A121.98 V (53.03%)108.0 V201.21 V (87.48%)57940.5 WDrop High
16 mm²76 A59 A76.24 V (33.15%)153.8 V125.76 V (54.68%)36212.8 WDrop High
25 mm²101 A78 A48.79 V (21.21%)181.2 V80.48 V (34.99%)23176.2 WDrop High
35 mm²125 A97 A34.85 V (15.15%)195.1 V57.49 V (25.0%)16554.4 WDrop High
50 mm²151 A118 A24.4 V (10.61%)205.6 V40.24 V (17.5%)11588.1 WDrop High
70 mm²192 A150 A17.43 V (7.58%)212.6 V28.74 V (12.5%)8277.2 WDrop High
95 mm²232 A181 A12.84 V (5.58%)217.2 V21.18 V (9.21%)6099.0 WDrop High
120 mm²269 A210 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 WDrop High
150 mm²309 A241 A8.13 V (3.54%)221.9 V13.41 V (5.83%)3862.7 WDrop High
185 mm²353 A275 A6.59 V (2.87%)223.4 V10.88 V (4.73%)3131.9 WDrop High
240 mm²415 A324 A5.08 V (2.21%)224.9 V8.38 V (3.65%)2414.2 WDrop High
300 mm²477 A372 A4.07 V (1.77%)225.9 V6.71 V (2.92%)1931.3 W✓ OK (≤3%)
400 mm²570 A445 A3.05 V (1.33%)227.0 V5.03 V (2.19%)1448.5 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 60 Meter (230V)

Vilken kabelarea krävs för 475A vid 60 meter (230V)?

För 475 Ampere över 60 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (4.07V / 1.77%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.