Kabelarea för 475 Ampere vid 60 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 60 m vid 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 4.07V (1.77%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.03V (2.19%)
Voltage at Load225.9 VLine Loss: 1931.3 W
Max Power & Breaker109.25 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 813.2 V (353.57%) | 0.0 V | 1341.4 V (583.22%) | 386270.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 487.92 V (212.14%) | 0.0 V | 804.84 V (349.93%) | 231762.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 304.95 V (132.59%) | 0.0 V | 503.02 V (218.71%) | 144851.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 203.3 V (88.39%) | 26.7 V | 335.35 V (145.8%) | 96567.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 121.98 V (53.03%) | 108.0 V | 201.21 V (87.48%) | 57940.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 76.24 V (33.15%) | 153.8 V | 125.76 V (54.68%) | 36212.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 48.79 V (21.21%) | 181.2 V | 80.48 V (34.99%) | 23176.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 34.85 V (15.15%) | 195.1 V | 57.49 V (25.0%) | 16554.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 24.4 V (10.61%) | 205.6 V | 40.24 V (17.5%) | 11588.1 W | Drop High |
| 70 mm² | 192 A | 150 A | 17.43 V (7.58%) | 212.6 V | 28.74 V (12.5%) | 8277.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 12.84 V (5.58%) | 217.2 V | 21.18 V (9.21%) | 6099.0 W | Drop High |
| 120 mm² | 269 A | 210 A | 10.16 V (4.42%) | 219.8 V | 16.77 V (7.29%) | 4828.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 8.13 V (3.54%) | 221.9 V | 13.41 V (5.83%) | 3862.7 W | Drop High |
| 185 mm² | 353 A | 275 A | 6.59 V (2.87%) | 223.4 V | 10.88 V (4.73%) | 3131.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 5.08 V (2.21%) | 224.9 V | 8.38 V (3.65%) | 2414.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 4.07 V (1.77%) | 225.9 V | 6.71 V (2.92%) | 1931.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.05 V (1.33%) | 227.0 V | 5.03 V (2.19%) | 1448.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 475 Ampere vid 60 Meter (230V)
Vilken kabelarea krävs för 475A vid 60 meter (230V)?
För 475 Ampere över 60 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (4.07V / 1.77%).
Hur stor effekt motsvarar 475A vid 230V?
Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.
Related Lengths & Currents (230V)
475A · 5m (230V)475A · 10m (230V)475A · 15m (230V)475A · 20m (230V)475A · 25m (230V)475A · 30m (230V)475A · 35m (230V)475A · 40m (230V)475A · 45m (230V)475A · 50m (230V)475A · 70m (230V)10A · 60m (230V)16A · 60m (230V)20A · 60m (230V)25A · 60m (230V)32A · 60m (230V)40A · 60m (230V)50A · 60m (230V)63A · 60m (230V)80A · 60m (230V)100A · 60m (230V)125A · 60m (230V)160A · 60m (230V)200A · 60m (230V)