Kabelarea för 475 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 35 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.37V (1.03%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.93V (1.28%)
Voltage at Load227.6 VLine Loss: 1126.6 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A474.37 V (206.25%)0.0 V782.48 V (340.21%)225324.2 WDrop High
2.5 mm²24 A18 A284.62 V (123.75%)0.0 V469.49 V (204.13%)135194.5 WDrop High
4 mm²32 A25 A177.89 V (77.34%)52.1 V293.43 V (127.58%)84496.6 WDrop High
6 mm²41 A32 A118.59 V (51.56%)111.4 V195.62 V (85.05%)56331.0 WDrop High
10 mm²57 A44 A71.16 V (30.94%)158.8 V117.37 V (51.03%)33798.6 WDrop High
16 mm²76 A59 A44.47 V (19.34%)185.5 V73.36 V (31.89%)21124.1 WDrop High
25 mm²101 A78 A28.46 V (12.37%)201.5 V46.95 V (20.41%)13519.5 WDrop High
35 mm²125 A97 A20.33 V (8.84%)209.7 V33.53 V (14.58%)9656.8 WDrop High
50 mm²151 A118 A14.23 V (6.19%)215.8 V23.47 V (10.21%)6759.7 WDrop High
70 mm²192 A150 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 WDrop High
95 mm²232 A181 A7.49 V (3.26%)222.5 V12.36 V (5.37%)3557.7 WDrop High
120 mm²269 A210 A5.93 V (2.58%)224.1 V9.78 V (4.25%)2816.6 WDrop High
150 mm²309 A241 A4.74 V (2.06%)225.3 V7.82 V (3.4%)2253.2 WDrop High
185 mm²353 A275 A3.85 V (1.67%)226.2 V6.34 V (2.76%)1827.0 WDrop High
240 mm²415 A324 A2.96 V (1.29%)227.0 V4.89 V (2.13%)1408.3 WDrop High
300 mm²477 A372 A2.37 V (1.03%)227.6 V3.91 V (1.7%)1126.6 W✓ OK (≤3%)
400 mm²570 A445 A1.78 V (0.77%)228.2 V2.93 V (1.28%)845.0 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 475A vid 35 meter (230V)?

För 475 Ampere över 35 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.37V / 1.03%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.