Kabelarea för 475 Ampere vid 30 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 30 m vid 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 2.03V (0.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.52V (1.09%)
Voltage at Load228.0 VLine Loss: 965.7 W
Max Power & Breaker109.25 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 406.6 V (176.78%) | 0.0 V | 670.7 V (291.61%) | 193135.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 243.96 V (106.07%) | 0.0 V | 402.42 V (174.97%) | 115881.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 152.47 V (66.29%) | 77.5 V | 251.51 V (109.35%) | 72425.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 101.65 V (44.2%) | 128.4 V | 167.67 V (72.9%) | 48283.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 60.99 V (26.52%) | 169.0 V | 100.6 V (43.74%) | 28970.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 38.12 V (16.57%) | 191.9 V | 62.88 V (27.34%) | 18106.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 24.4 V (10.61%) | 205.6 V | 40.24 V (17.5%) | 11588.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 17.43 V (7.58%) | 212.6 V | 28.74 V (12.5%) | 8277.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 12.2 V (5.3%) | 217.8 V | 20.12 V (8.75%) | 5794.1 W | Drop High |
| 70 mm² | 192 A | 150 A | 8.71 V (3.79%) | 221.3 V | 14.37 V (6.25%) | 4138.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 6.42 V (2.79%) | 223.6 V | 10.59 V (4.6%) | 3049.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 5.08 V (2.21%) | 224.9 V | 8.38 V (3.65%) | 2414.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.07 V (1.77%) | 225.9 V | 6.71 V (2.92%) | 1931.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.3 V (1.43%) | 226.7 V | 5.44 V (2.36%) | 1566.0 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.54 V (1.1%) | 227.5 V | 4.19 V (1.82%) | 1207.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.03 V (0.88%) | 228.0 V | 3.35 V (1.46%) | 965.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.52 V (0.66%) | 228.5 V | 2.52 V (1.09%) | 724.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 475 Ampere vid 30 Meter (230V)
Vilken kabelarea krävs för 475A vid 30 meter (230V)?
För 475 Ampere över 30 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.03V / 0.88%).
Hur stor effekt motsvarar 475A vid 230V?
Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.
Related Lengths & Currents (230V)
475A · 5m (230V)475A · 10m (230V)475A · 15m (230V)475A · 20m (230V)475A · 25m (230V)475A · 35m (230V)475A · 40m (230V)475A · 45m (230V)475A · 50m (230V)475A · 60m (230V)475A · 70m (230V)10A · 30m (230V)16A · 30m (230V)20A · 30m (230V)25A · 30m (230V)32A · 30m (230V)40A · 30m (230V)50A · 30m (230V)63A · 30m (230V)80A · 30m (230V)100A · 30m (230V)125A · 30m (230V)160A · 30m (230V)200A · 30m (230V)