Kabelarea för 475 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 30 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.03V (0.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.52V (1.09%)
Voltage at Load228.0 VLine Loss: 965.7 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A406.6 V (176.78%)0.0 V670.7 V (291.61%)193135.0 WDrop High
2.5 mm²24 A18 A243.96 V (106.07%)0.0 V402.42 V (174.97%)115881.0 WDrop High
4 mm²32 A25 A152.47 V (66.29%)77.5 V251.51 V (109.35%)72425.6 WDrop High
6 mm²41 A32 A101.65 V (44.2%)128.4 V167.67 V (72.9%)48283.8 WDrop High
10 mm²57 A44 A60.99 V (26.52%)169.0 V100.6 V (43.74%)28970.3 WDrop High
16 mm²76 A59 A38.12 V (16.57%)191.9 V62.88 V (27.34%)18106.4 WDrop High
25 mm²101 A78 A24.4 V (10.61%)205.6 V40.24 V (17.5%)11588.1 WDrop High
35 mm²125 A97 A17.43 V (7.58%)212.6 V28.74 V (12.5%)8277.2 WDrop High
50 mm²151 A118 A12.2 V (5.3%)217.8 V20.12 V (8.75%)5794.1 WDrop High
70 mm²192 A150 A8.71 V (3.79%)221.3 V14.37 V (6.25%)4138.6 WDrop High
95 mm²232 A181 A6.42 V (2.79%)223.6 V10.59 V (4.6%)3049.5 WDrop High
120 mm²269 A210 A5.08 V (2.21%)224.9 V8.38 V (3.65%)2414.2 WDrop High
150 mm²309 A241 A4.07 V (1.77%)225.9 V6.71 V (2.92%)1931.3 WDrop High
185 mm²353 A275 A3.3 V (1.43%)226.7 V5.44 V (2.36%)1566.0 WDrop High
240 mm²415 A324 A2.54 V (1.1%)227.5 V4.19 V (1.82%)1207.1 WDrop High
300 mm²477 A372 A2.03 V (0.88%)228.0 V3.35 V (1.46%)965.7 W✓ OK (≤3%)
400 mm²570 A445 A1.52 V (0.66%)228.5 V2.52 V (1.09%)724.3 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 475A vid 30 meter (230V)?

För 475 Ampere över 30 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.03V / 0.88%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.