⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 475 Ampere vid 40 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 40 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.71V (1.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.35V (1.46%)
Voltage at Load227.3 VLine Loss: 1287.6 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A542.13 V (235.71%)0.0 V894.27 V (388.81%)257513.3 WDrop High
2.5 mm²24 A18 A325.28 V (141.43%)0.0 V536.56 V (233.29%)154508.0 WDrop High
4 mm²32 A25 A203.3 V (88.39%)26.7 V335.35 V (145.8%)96567.5 WDrop High
6 mm²41 A32 A135.53 V (58.93%)94.5 V223.57 V (97.2%)64378.3 WDrop High
10 mm²57 A44 A81.32 V (35.36%)148.7 V134.14 V (58.32%)38627.0 WDrop High
16 mm²76 A59 A50.82 V (22.1%)179.2 V83.84 V (36.45%)24141.9 WDrop High
25 mm²101 A78 A32.53 V (14.14%)197.5 V53.66 V (23.33%)15450.8 WDrop High
35 mm²125 A97 A23.23 V (10.1%)206.8 V38.33 V (16.66%)11036.3 WDrop High
50 mm²151 A118 A16.26 V (7.07%)213.7 V26.83 V (11.66%)7725.4 WDrop High
70 mm²192 A150 A11.62 V (5.05%)218.4 V19.16 V (8.33%)5518.1 WDrop High
95 mm²232 A181 A8.56 V (3.72%)221.4 V14.12 V (6.14%)4066.0 WDrop High
120 mm²269 A210 A6.78 V (2.95%)223.2 V11.18 V (4.86%)3218.9 WDrop High
150 mm²309 A241 A5.42 V (2.36%)224.6 V8.94 V (3.89%)2575.1 WDrop High
185 mm²353 A275 A4.4 V (1.91%)225.6 V7.25 V (3.15%)2087.9 WDrop High
240 mm²415 A324 A3.39 V (1.47%)226.6 V5.59 V (2.43%)1609.5 WDrop High
300 mm²477 A372 A2.71 V (1.18%)227.3 V4.47 V (1.94%)1287.6 W✓ OK (≤3%)
400 mm²570 A445 A2.03 V (0.88%)228.0 V3.35 V (1.46%)965.7 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 40 Meter (230V)

Vilken kabelarea krävs för 475A vid 40 meter (230V)?

För 475 Ampere över 40 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.71V / 1.18%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.