Kabelarea för 475 Ampere vid 150 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 150 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.81V (1.66%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.58V (5.47%)
Voltage at Load226.2 VLine Loss: 1810.7 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2033.0 V (883.91%)0.0 V3353.5 V (1458.04%)965675.0 WDrop High
2.5 mm²24 A18 A1219.8 V (530.35%)0.0 V2012.1 V (874.83%)579405.0 WDrop High
4 mm²32 A25 A762.38 V (331.47%)0.0 V1257.56 V (546.77%)362128.1 WDrop High
6 mm²41 A32 A508.25 V (220.98%)0.0 V838.38 V (364.51%)241418.8 WDrop High
10 mm²57 A44 A304.95 V (132.59%)0.0 V503.02 V (218.71%)144851.2 WDrop High
16 mm²76 A59 A190.59 V (82.87%)39.4 V314.39 V (136.69%)90532.0 WDrop High
25 mm²101 A78 A121.98 V (53.03%)108.0 V201.21 V (87.48%)57940.5 WDrop High
35 mm²125 A97 A87.13 V (37.88%)142.9 V143.72 V (62.49%)41386.1 WDrop High
50 mm²151 A118 A60.99 V (26.52%)169.0 V100.6 V (43.74%)28970.2 WDrop High
70 mm²192 A150 A43.56 V (18.94%)186.4 V71.86 V (31.24%)20693.0 WDrop High
95 mm²232 A181 A32.1 V (13.96%)197.9 V52.95 V (23.02%)15247.5 WDrop High
120 mm²269 A210 A25.41 V (11.05%)204.6 V41.92 V (18.23%)12070.9 WDrop High
150 mm²309 A241 A20.33 V (8.84%)209.7 V33.53 V (14.58%)9656.8 WDrop High
185 mm²353 A275 A16.48 V (7.17%)213.5 V27.19 V (11.82%)7829.8 WDrop High
240 mm²415 A324 A12.71 V (5.52%)217.3 V20.96 V (9.11%)6035.5 WDrop High
300 mm²477 A372 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 W~ ≤5%
400 mm²570 A445 A7.62 V (3.31%)222.4 V12.58 V (5.47%)3621.3 W~ ≤5%

FAQ — Kabelarea för 475 Ampere vid 150 Meter (230V)

Vilken kabelarea krävs för 475A vid 150 meter (230V)?

För 475 Ampere över 150 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.81V / 1.66%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.