Kabelarea för 475 Ampere vid 150 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 150 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.81V (1.66%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.58V (5.47%)
Voltage at Load226.2 VLine Loss: 1810.7 W
Max Power & Breaker109.25 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2033.0 V (883.91%) | 0.0 V | 3353.5 V (1458.04%) | 965675.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1219.8 V (530.35%) | 0.0 V | 2012.1 V (874.83%) | 579405.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 762.38 V (331.47%) | 0.0 V | 1257.56 V (546.77%) | 362128.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 508.25 V (220.98%) | 0.0 V | 838.38 V (364.51%) | 241418.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 304.95 V (132.59%) | 0.0 V | 503.02 V (218.71%) | 144851.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 190.59 V (82.87%) | 39.4 V | 314.39 V (136.69%) | 90532.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 121.98 V (53.03%) | 108.0 V | 201.21 V (87.48%) | 57940.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 87.13 V (37.88%) | 142.9 V | 143.72 V (62.49%) | 41386.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 60.99 V (26.52%) | 169.0 V | 100.6 V (43.74%) | 28970.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 43.56 V (18.94%) | 186.4 V | 71.86 V (31.24%) | 20693.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 32.1 V (13.96%) | 197.9 V | 52.95 V (23.02%) | 15247.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 25.41 V (11.05%) | 204.6 V | 41.92 V (18.23%) | 12070.9 W | Drop High |
| 150 mm² | 309 A | 241 A | 20.33 V (8.84%) | 209.7 V | 33.53 V (14.58%) | 9656.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 16.48 V (7.17%) | 213.5 V | 27.19 V (11.82%) | 7829.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 12.71 V (5.52%) | 217.3 V | 20.96 V (9.11%) | 6035.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 10.16 V (4.42%) | 219.8 V | 16.77 V (7.29%) | 4828.4 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 7.62 V (3.31%) | 222.4 V | 12.58 V (5.47%) | 3621.3 W | ~ ≤5% |
FAQ — Kabelarea för 475 Ampere vid 150 Meter (230V)
Vilken kabelarea krävs för 475A vid 150 meter (230V)?
För 475 Ampere över 150 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.81V / 1.66%).
Hur stor effekt motsvarar 475A vid 230V?
Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.
Related Lengths & Currents (230V)
475A · 5m (230V)475A · 10m (230V)475A · 15m (230V)475A · 20m (230V)475A · 25m (230V)475A · 30m (230V)475A · 35m (230V)475A · 40m (230V)475A · 45m (230V)475A · 50m (230V)475A · 60m (230V)475A · 70m (230V)10A · 150m (230V)16A · 150m (230V)20A · 150m (230V)25A · 150m (230V)32A · 150m (230V)40A · 150m (230V)50A · 150m (230V)63A · 150m (230V)80A · 150m (230V)100A · 150m (230V)125A · 150m (230V)160A · 150m (230V)200A · 150m (230V)