Kabelarea för 475 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 150 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 8.8V (2.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.89V (2.72%)
Voltage at Load391.2 VLine Loss: 7242.6 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1760.63 V (440.16%)0.0 V2904.22 V (726.05%)1448512.5 WDrop High
2.5 mm²24 A18 A1056.38 V (264.09%)0.0 V1742.53 V (435.63%)869107.5 WDrop High
4 mm²32 A25 A660.24 V (165.06%)0.0 V1089.08 V (272.27%)543192.2 WDrop High
6 mm²41 A32 A440.16 V (110.04%)0.0 V726.05 V (181.51%)362128.1 WDrop High
10 mm²57 A44 A264.09 V (66.02%)135.9 V435.63 V (108.91%)217276.9 WDrop High
16 mm²76 A59 A165.06 V (41.26%)234.9 V272.27 V (68.07%)135798.0 WDrop High
25 mm²101 A78 A105.64 V (26.41%)294.4 V174.25 V (43.56%)86910.7 WDrop High
35 mm²125 A97 A75.46 V (18.86%)324.5 V124.47 V (31.12%)62079.1 WDrop High
50 mm²151 A118 A52.82 V (13.2%)347.2 V87.13 V (21.78%)43455.4 WDrop High
70 mm²192 A150 A37.73 V (9.43%)362.3 V62.23 V (15.56%)31039.6 WDrop High
95 mm²232 A181 A27.8 V (6.95%)372.2 V45.86 V (11.46%)22871.2 WDrop High
120 mm²269 A210 A22.01 V (5.5%)378.0 V36.3 V (9.08%)18106.4 WDrop High
150 mm²309 A241 A17.61 V (4.4%)382.4 V29.04 V (7.26%)14485.1 WDrop High
185 mm²353 A275 A14.28 V (3.57%)385.7 V23.55 V (5.89%)11744.7 WDrop High
240 mm²415 A324 A11.0 V (2.75%)389.0 V18.15 V (4.54%)9053.2 WDrop High
300 mm²477 A372 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 W✓ OK (≤3%)
400 mm²570 A445 A6.6 V (1.65%)393.4 V10.89 V (2.72%)5431.9 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 475A vid 150 meter (400V)?

För 475 Ampere över 150 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (8.8V / 2.2%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.