Kabelarea för 475 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 250 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 11.0V (2.75%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.15V (4.54%)
Voltage at Load389.0 VLine Loss: 9053.2 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2934.38 V (733.6%)0.0 V4840.36 V (1210.09%)2414187.5 WDrop High
2.5 mm²24 A18 A1760.63 V (440.16%)0.0 V2904.22 V (726.05%)1448512.5 WDrop High
4 mm²32 A25 A1100.39 V (275.1%)0.0 V1815.14 V (453.78%)905320.3 WDrop High
6 mm²41 A32 A733.6 V (183.4%)0.0 V1210.09 V (302.52%)603546.9 WDrop High
10 mm²57 A44 A440.16 V (110.04%)0.0 V726.05 V (181.51%)362128.1 WDrop High
16 mm²76 A59 A275.1 V (68.77%)124.9 V453.78 V (113.45%)226330.1 WDrop High
25 mm²101 A78 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
35 mm²125 A97 A125.76 V (31.44%)274.2 V207.44 V (51.86%)103465.2 WDrop High
50 mm²151 A118 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
70 mm²192 A150 A62.88 V (15.72%)337.1 V103.72 V (25.93%)51732.6 WDrop High
95 mm²232 A181 A46.33 V (11.58%)353.7 V76.43 V (19.11%)38118.8 WDrop High
120 mm²269 A210 A36.68 V (9.17%)363.3 V60.5 V (15.13%)30177.3 WDrop High
150 mm²309 A241 A29.34 V (7.34%)370.7 V48.4 V (12.1%)24141.9 WDrop High
185 mm²353 A275 A23.79 V (5.95%)376.2 V39.25 V (9.81%)19574.5 WDrop High
240 mm²415 A324 A18.34 V (4.58%)381.7 V30.25 V (7.56%)15088.7 WDrop High
300 mm²477 A372 A14.67 V (3.67%)385.3 V24.2 V (6.05%)12070.9 W~ ≤5%
400 mm²570 A445 A11.0 V (2.75%)389.0 V18.15 V (4.54%)9053.2 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 475A vid 250 meter (400V)?

För 475 Ampere över 250 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.0V / 2.75%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.