Kabelarea för 600 Ampere vid 175 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 175 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.87V (1.22%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (4.01%)
Voltage at Load395.1 VLine Loss: 5055.8 W
Max Power & Breaker415.69 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2594.61 V (648.65%) | 0.0 V | 4279.9 V (1069.97%) | 2696400.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1556.77 V (389.19%) | 0.0 V | 2567.94 V (641.98%) | 1617840.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 972.98 V (243.24%) | 0.0 V | 1604.96 V (401.24%) | 1011150.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 648.65 V (162.16%) | 0.0 V | 1069.97 V (267.49%) | 674100.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 389.19 V (97.3%) | 10.8 V | 641.98 V (160.5%) | 404460.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 243.24 V (60.81%) | 156.8 V | 401.24 V (100.31%) | 252787.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 155.68 V (38.92%) | 244.3 V | 256.79 V (64.2%) | 161784.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 111.2 V (27.8%) | 288.8 V | 183.42 V (45.86%) | 115560.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 77.84 V (19.46%) | 322.2 V | 128.4 V (32.1%) | 80892.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 55.6 V (13.9%) | 344.4 V | 91.71 V (22.93%) | 57780.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 40.97 V (10.24%) | 359.0 V | 67.58 V (16.89%) | 42574.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 32.43 V (8.11%) | 367.6 V | 53.5 V (13.37%) | 33705.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 26964.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 21.04 V (5.26%) | 379.0 V | 34.7 V (8.68%) | 21862.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 16.22 V (4.05%) | 383.8 V | 26.75 V (6.69%) | 16852.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 13482.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 9.73 V (2.43%) | 390.3 V | 16.05 V (4.01%) | 10111.5 W | Drop High |
FAQ — Kabelarea för 600 Ampere vid 175 Meter (400V)
Vilken kabelarea krävs för 600A vid 175 meter (400V)?
För 600 Ampere över 175 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.87V / 1.22%).
Hur stor effekt motsvarar 600A vid 400V?
Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.
Related Lengths & Currents (400V)
600A · 5m (400V)600A · 10m (400V)600A · 15m (400V)600A · 20m (400V)600A · 25m (400V)600A · 30m (400V)600A · 35m (400V)600A · 40m (400V)600A · 45m (400V)600A · 50m (400V)600A · 60m (400V)600A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)