Kabelarea för 600 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 175 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.87V (1.22%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (4.01%)
Voltage at Load395.1 VLine Loss: 5055.8 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2594.61 V (648.65%)0.0 V4279.9 V (1069.97%)2696400.0 WDrop High
2.5 mm²24 A18 A1556.77 V (389.19%)0.0 V2567.94 V (641.98%)1617840.0 WDrop High
4 mm²32 A25 A972.98 V (243.24%)0.0 V1604.96 V (401.24%)1011150.0 WDrop High
6 mm²41 A32 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)674100.0 WDrop High
10 mm²57 A44 A389.19 V (97.3%)10.8 V641.98 V (160.5%)404460.0 WDrop High
16 mm²76 A59 A243.24 V (60.81%)156.8 V401.24 V (100.31%)252787.5 WDrop High
25 mm²101 A78 A155.68 V (38.92%)244.3 V256.79 V (64.2%)161784.0 WDrop High
35 mm²125 A97 A111.2 V (27.8%)288.8 V183.42 V (45.86%)115560.0 WDrop High
50 mm²151 A118 A77.84 V (19.46%)322.2 V128.4 V (32.1%)80892.0 WDrop High
70 mm²192 A150 A55.6 V (13.9%)344.4 V91.71 V (22.93%)57780.0 WDrop High
95 mm²232 A181 A40.97 V (10.24%)359.0 V67.58 V (16.89%)42574.7 WDrop High
120 mm²269 A210 A32.43 V (8.11%)367.6 V53.5 V (13.37%)33705.0 WDrop High
150 mm²309 A241 A25.95 V (6.49%)374.1 V42.8 V (10.7%)26964.0 WDrop High
185 mm²353 A275 A21.04 V (5.26%)379.0 V34.7 V (8.68%)21862.7 WDrop High
240 mm²415 A324 A16.22 V (4.05%)383.8 V26.75 V (6.69%)16852.5 WDrop High
300 mm²477 A372 A12.97 V (3.24%)387.0 V21.4 V (5.35%)13482.0 WDrop High
400 mm²570 A445 A9.73 V (2.43%)390.3 V16.05 V (4.01%)10111.5 WDrop High

FAQ — Kabelarea för 600 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 600A vid 175 meter (400V)?

För 600 Ampere över 175 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.87V / 1.22%).

Hur stor effekt motsvarar 600A vid 400V?

Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.