⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 650 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 15 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.45V (0.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.49V (0.37%)
Voltage at Load399.6 VLine Loss: 508.6 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A240.93 V (60.23%)159.1 V397.42 V (99.35%)271245.0 WDrop High
2.5 mm²24 A18 A144.56 V (36.14%)255.4 V238.45 V (59.61%)162747.0 WDrop High
4 mm²32 A25 A90.35 V (22.59%)309.7 V149.03 V (37.26%)101716.9 WDrop High
6 mm²41 A32 A60.23 V (15.06%)339.8 V99.35 V (24.84%)67811.2 WDrop High
10 mm²57 A44 A36.14 V (9.03%)363.9 V59.61 V (14.9%)40686.8 WDrop High
16 mm²76 A59 A22.59 V (5.65%)377.4 V37.26 V (9.31%)25429.2 WDrop High
25 mm²101 A78 A14.46 V (3.61%)385.5 V23.85 V (5.96%)16274.7 WDrop High
35 mm²125 A97 A10.33 V (2.58%)389.7 V17.03 V (4.26%)11624.8 WDrop High
50 mm²151 A118 A7.23 V (1.81%)392.8 V11.92 V (2.98%)8137.4 WDrop High
70 mm²192 A150 A5.16 V (1.29%)394.8 V8.52 V (2.13%)5812.4 WDrop High
95 mm²232 A181 A3.8 V (0.95%)396.2 V6.28 V (1.57%)4282.8 WDrop High
120 mm²269 A210 A3.01 V (0.75%)397.0 V4.97 V (1.24%)3390.6 WDrop High
150 mm²309 A241 A2.41 V (0.6%)397.6 V3.97 V (0.99%)2712.4 WDrop High
185 mm²353 A275 A1.95 V (0.49%)398.0 V3.22 V (0.81%)2199.3 WDrop High
240 mm²415 A324 A1.51 V (0.38%)398.5 V2.48 V (0.62%)1695.3 WDrop High
300 mm²477 A372 A1.2 V (0.3%)398.8 V1.99 V (0.5%)1356.2 WDrop High
400 mm²570 A445 A0.9 V (0.23%)399.1 V1.49 V (0.37%)1017.2 WDrop High

FAQ — Kabelarea för 650 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 650A vid 15 meter (400V)?

För 650 Ampere över 15 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.45V / 0.12%).

Hur stor effekt motsvarar 650A vid 400V?

Det motsvarar 450.33 kW med en rekommenderad säkring på 700A.