Kabelarea för 650 Ampere vid 15 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 15 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.45V (0.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.49V (0.37%)
Voltage at Load399.6 VLine Loss: 508.6 W
Max Power & Breaker450.33 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 240.93 V (60.23%) | 159.1 V | 397.42 V (99.35%) | 271245.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 144.56 V (36.14%) | 255.4 V | 238.45 V (59.61%) | 162747.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 90.35 V (22.59%) | 309.7 V | 149.03 V (37.26%) | 101716.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 60.23 V (15.06%) | 339.8 V | 99.35 V (24.84%) | 67811.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 36.14 V (9.03%) | 363.9 V | 59.61 V (14.9%) | 40686.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 22.59 V (5.65%) | 377.4 V | 37.26 V (9.31%) | 25429.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 14.46 V (3.61%) | 385.5 V | 23.85 V (5.96%) | 16274.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 10.33 V (2.58%) | 389.7 V | 17.03 V (4.26%) | 11624.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 7.23 V (1.81%) | 392.8 V | 11.92 V (2.98%) | 8137.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 5.16 V (1.29%) | 394.8 V | 8.52 V (2.13%) | 5812.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.8 V (0.95%) | 396.2 V | 6.28 V (1.57%) | 4282.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 3.01 V (0.75%) | 397.0 V | 4.97 V (1.24%) | 3390.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.41 V (0.6%) | 397.6 V | 3.97 V (0.99%) | 2712.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.95 V (0.49%) | 398.0 V | 3.22 V (0.81%) | 2199.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.51 V (0.38%) | 398.5 V | 2.48 V (0.62%) | 1695.3 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.2 V (0.3%) | 398.8 V | 1.99 V (0.5%) | 1356.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.9 V (0.23%) | 399.1 V | 1.49 V (0.37%) | 1017.2 W | Drop High |
FAQ — Kabelarea för 650 Ampere vid 15 Meter (400V)
Vilken kabelarea krävs för 650A vid 15 meter (400V)?
För 650 Ampere över 15 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.45V / 0.12%).
Hur stor effekt motsvarar 650A vid 400V?
Det motsvarar 450.33 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (400V)
650A · 5m (400V)650A · 10m (400V)650A · 20m (400V)650A · 25m (400V)650A · 30m (400V)650A · 35m (400V)650A · 40m (400V)650A · 45m (400V)650A · 50m (400V)650A · 60m (400V)650A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)25A · 15m (400V)32A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)125A · 15m (400V)160A · 15m (400V)200A · 15m (400V)