Kabelarea för 650 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 60 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.8V (0.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.96V (1.49%)
Voltage at Load398.2 VLine Loss: 2034.3 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A963.71 V (240.93%)0.0 V1589.68 V (397.42%)1084980.0 WDrop High
2.5 mm²24 A18 A578.23 V (144.56%)0.0 V953.81 V (238.45%)650988.0 WDrop High
4 mm²32 A25 A361.39 V (90.35%)38.6 V596.13 V (149.03%)406867.5 WDrop High
6 mm²41 A32 A240.93 V (60.23%)159.1 V397.42 V (99.35%)271245.0 WDrop High
10 mm²57 A44 A144.56 V (36.14%)255.4 V238.45 V (59.61%)162747.0 WDrop High
16 mm²76 A59 A90.35 V (22.59%)309.7 V149.03 V (37.26%)101716.9 WDrop High
25 mm²101 A78 A57.82 V (14.46%)342.2 V95.38 V (23.85%)65098.8 WDrop High
35 mm²125 A97 A41.3 V (10.33%)358.7 V68.13 V (17.03%)46499.1 WDrop High
50 mm²151 A118 A28.91 V (7.23%)371.1 V47.69 V (11.92%)32549.4 WDrop High
70 mm²192 A150 A20.65 V (5.16%)379.3 V34.06 V (8.52%)23249.6 WDrop High
95 mm²232 A181 A15.22 V (3.8%)384.8 V25.1 V (6.28%)17131.3 WDrop High
120 mm²269 A210 A12.05 V (3.01%)388.0 V19.87 V (4.97%)13562.2 WDrop High
150 mm²309 A241 A9.64 V (2.41%)390.4 V15.9 V (3.97%)10849.8 WDrop High
185 mm²353 A275 A7.81 V (1.95%)392.2 V12.89 V (3.22%)8797.1 WDrop High
240 mm²415 A324 A6.02 V (1.51%)394.0 V9.94 V (2.48%)6781.1 WDrop High
300 mm²477 A372 A4.82 V (1.2%)395.2 V7.95 V (1.99%)5424.9 WDrop High
400 mm²570 A445 A3.61 V (0.9%)396.4 V5.96 V (1.49%)4068.7 WDrop High

FAQ — Kabelarea för 650 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 650A vid 60 meter (400V)?

För 650 Ampere över 60 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.8V / 0.45%).

Hur stor effekt motsvarar 650A vid 400V?

Det motsvarar 450.33 kW med en rekommenderad säkring på 700A.