Kabelarea för 650 Ampere vid 60 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 60 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.8V (0.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.96V (1.49%)
Voltage at Load398.2 VLine Loss: 2034.3 W
Max Power & Breaker450.33 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 963.71 V (240.93%) | 0.0 V | 1589.68 V (397.42%) | 1084980.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 578.23 V (144.56%) | 0.0 V | 953.81 V (238.45%) | 650988.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 361.39 V (90.35%) | 38.6 V | 596.13 V (149.03%) | 406867.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 240.93 V (60.23%) | 159.1 V | 397.42 V (99.35%) | 271245.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 144.56 V (36.14%) | 255.4 V | 238.45 V (59.61%) | 162747.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 90.35 V (22.59%) | 309.7 V | 149.03 V (37.26%) | 101716.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 57.82 V (14.46%) | 342.2 V | 95.38 V (23.85%) | 65098.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 41.3 V (10.33%) | 358.7 V | 68.13 V (17.03%) | 46499.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 28.91 V (7.23%) | 371.1 V | 47.69 V (11.92%) | 32549.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 20.65 V (5.16%) | 379.3 V | 34.06 V (8.52%) | 23249.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 15.22 V (3.8%) | 384.8 V | 25.1 V (6.28%) | 17131.3 W | Drop High |
| 120 mm² | 269 A | 210 A | 12.05 V (3.01%) | 388.0 V | 19.87 V (4.97%) | 13562.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 9.64 V (2.41%) | 390.4 V | 15.9 V (3.97%) | 10849.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 7.81 V (1.95%) | 392.2 V | 12.89 V (3.22%) | 8797.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 6.02 V (1.51%) | 394.0 V | 9.94 V (2.48%) | 6781.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 4.82 V (1.2%) | 395.2 V | 7.95 V (1.99%) | 5424.9 W | Drop High |
| 400 mm² | 570 A | 445 A | 3.61 V (0.9%) | 396.4 V | 5.96 V (1.49%) | 4068.7 W | Drop High |
FAQ — Kabelarea för 650 Ampere vid 60 Meter (400V)
Vilken kabelarea krävs för 650A vid 60 meter (400V)?
För 650 Ampere över 60 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.8V / 0.45%).
Hur stor effekt motsvarar 650A vid 400V?
Det motsvarar 450.33 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (400V)
650A · 5m (400V)650A · 10m (400V)650A · 15m (400V)650A · 20m (400V)650A · 25m (400V)650A · 30m (400V)650A · 35m (400V)650A · 40m (400V)650A · 45m (400V)650A · 50m (400V)650A · 70m (400V)10A · 60m (400V)16A · 60m (400V)20A · 60m (400V)25A · 60m (400V)32A · 60m (400V)40A · 60m (400V)50A · 60m (400V)63A · 60m (400V)80A · 60m (400V)100A · 60m (400V)125A · 60m (400V)160A · 60m (400V)200A · 60m (400V)