Kabelarea för 650 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 35 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.05V (0.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.48V (0.87%)
Voltage at Load398.9 VLine Loss: 1186.7 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A562.17 V (140.54%)0.0 V927.31 V (231.83%)632905.0 WDrop High
2.5 mm²24 A18 A337.3 V (84.32%)62.7 V556.39 V (139.1%)379743.0 WDrop High
4 mm²32 A25 A210.81 V (52.7%)189.2 V347.74 V (86.94%)237339.4 WDrop High
6 mm²41 A32 A140.54 V (35.14%)259.5 V231.83 V (57.96%)158226.2 WDrop High
10 mm²57 A44 A84.32 V (21.08%)315.7 V139.1 V (34.77%)94935.8 WDrop High
16 mm²76 A59 A52.7 V (13.18%)347.3 V86.94 V (21.73%)59334.8 WDrop High
25 mm²101 A78 A33.73 V (8.43%)366.3 V55.64 V (13.91%)37974.3 WDrop High
35 mm²125 A97 A24.09 V (6.02%)375.9 V39.74 V (9.94%)27124.5 WDrop High
50 mm²151 A118 A16.86 V (4.22%)383.1 V27.82 V (6.95%)18987.2 WDrop High
70 mm²192 A150 A12.05 V (3.01%)388.0 V19.87 V (4.97%)13562.2 WDrop High
95 mm²232 A181 A8.88 V (2.22%)391.1 V14.64 V (3.66%)9993.2 WDrop High
120 mm²269 A210 A7.03 V (1.76%)393.0 V11.59 V (2.9%)7911.3 WDrop High
150 mm²309 A241 A5.62 V (1.41%)394.4 V9.27 V (2.32%)6329.1 WDrop High
185 mm²353 A275 A4.56 V (1.14%)395.4 V7.52 V (1.88%)5131.7 WDrop High
240 mm²415 A324 A3.51 V (0.88%)396.5 V5.8 V (1.45%)3955.7 WDrop High
300 mm²477 A372 A2.81 V (0.7%)397.2 V4.64 V (1.16%)3164.5 WDrop High
400 mm²570 A445 A2.11 V (0.53%)397.9 V3.48 V (0.87%)2373.4 WDrop High

FAQ — Kabelarea för 650 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 650A vid 35 meter (400V)?

För 650 Ampere över 35 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.05V / 0.27%).

Hur stor effekt motsvarar 650A vid 400V?

Det motsvarar 450.33 kW med en rekommenderad säkring på 700A.