Kabelarea för 700 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 120 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.5V (1.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.83V (6.45%)
Voltage at Load225.5 VLine Loss: 3145.8 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2396.8 V (1042.09%)0.0 V3953.6 V (1718.96%)1677760.0 WDrop High
2.5 mm²24 A18 A1438.08 V (625.25%)0.0 V2372.16 V (1031.37%)1006656.0 WDrop High
4 mm²32 A25 A898.8 V (390.78%)0.0 V1482.6 V (644.61%)629160.0 WDrop High
6 mm²41 A32 A599.2 V (260.52%)0.0 V988.4 V (429.74%)419440.0 WDrop High
10 mm²57 A44 A359.52 V (156.31%)0.0 V593.04 V (257.84%)251664.0 WDrop High
16 mm²76 A59 A224.7 V (97.7%)5.3 V370.65 V (161.15%)157290.0 WDrop High
25 mm²101 A78 A143.81 V (62.53%)86.2 V237.22 V (103.14%)100665.6 WDrop High
35 mm²125 A97 A102.72 V (44.66%)127.3 V169.44 V (73.67%)71904.0 WDrop High
50 mm²151 A118 A71.9 V (31.26%)158.1 V118.61 V (51.57%)50332.8 WDrop High
70 mm²192 A150 A51.36 V (22.33%)178.6 V84.72 V (36.83%)35952.0 WDrop High
95 mm²232 A181 A37.84 V (16.45%)192.2 V62.43 V (27.14%)26490.9 WDrop High
120 mm²269 A210 A29.96 V (13.03%)200.0 V49.42 V (21.49%)20972.0 WDrop High
150 mm²309 A241 A23.97 V (10.42%)206.0 V39.54 V (17.19%)16777.6 WDrop High
185 mm²353 A275 A19.43 V (8.45%)210.6 V32.06 V (13.94%)13603.5 WDrop High
240 mm²415 A324 A14.98 V (6.51%)215.0 V24.71 V (10.74%)10486.0 WDrop High
300 mm²477 A372 A11.98 V (5.21%)218.0 V19.77 V (8.59%)8388.8 WDrop High
400 mm²570 A445 A8.99 V (3.91%)221.0 V14.83 V (6.45%)6291.6 WDrop High

FAQ — Kabelarea för 700 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 700A vid 120 meter (230V)?

För 700 Ampere över 120 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.5V / 1.96%).

Hur stor effekt motsvarar 700A vid 230V?

Det motsvarar 161.0 kW med en rekommenderad säkring på 700A.