Kabelarea för 700 Ampere vid 120 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 120 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.5V (1.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.83V (6.45%)
Voltage at Load225.5 VLine Loss: 3145.8 W
Max Power & Breaker161.0 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 120m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2396.8 V (1042.09%) | 0.0 V | 3953.6 V (1718.96%) | 1677760.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1438.08 V (625.25%) | 0.0 V | 2372.16 V (1031.37%) | 1006656.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 898.8 V (390.78%) | 0.0 V | 1482.6 V (644.61%) | 629160.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 599.2 V (260.52%) | 0.0 V | 988.4 V (429.74%) | 419440.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 359.52 V (156.31%) | 0.0 V | 593.04 V (257.84%) | 251664.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 224.7 V (97.7%) | 5.3 V | 370.65 V (161.15%) | 157290.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 143.81 V (62.53%) | 86.2 V | 237.22 V (103.14%) | 100665.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 102.72 V (44.66%) | 127.3 V | 169.44 V (73.67%) | 71904.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 71.9 V (31.26%) | 158.1 V | 118.61 V (51.57%) | 50332.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 51.36 V (22.33%) | 178.6 V | 84.72 V (36.83%) | 35952.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 37.84 V (16.45%) | 192.2 V | 62.43 V (27.14%) | 26490.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 20972.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 23.97 V (10.42%) | 206.0 V | 39.54 V (17.19%) | 16777.6 W | Drop High |
| 185 mm² | 353 A | 275 A | 19.43 V (8.45%) | 210.6 V | 32.06 V (13.94%) | 13603.5 W | Drop High |
| 240 mm² | 415 A | 324 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 10486.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 11.98 V (5.21%) | 218.0 V | 19.77 V (8.59%) | 8388.8 W | Drop High |
| 400 mm² | 570 A | 445 A | 8.99 V (3.91%) | 221.0 V | 14.83 V (6.45%) | 6291.6 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 120 Meter (230V)
Vilken kabelarea krävs för 700A vid 120 meter (230V)?
För 700 Ampere över 120 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.5V / 1.96%).
Hur stor effekt motsvarar 700A vid 230V?
Det motsvarar 161.0 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (230V)
700A · 5m (230V)700A · 10m (230V)700A · 15m (230V)700A · 20m (230V)700A · 25m (230V)700A · 30m (230V)700A · 35m (230V)700A · 40m (230V)700A · 45m (230V)700A · 50m (230V)700A · 60m (230V)700A · 70m (230V)10A · 120m (230V)16A · 120m (230V)20A · 120m (230V)25A · 120m (230V)32A · 120m (230V)40A · 120m (230V)50A · 120m (230V)63A · 120m (230V)80A · 120m (230V)100A · 120m (230V)125A · 120m (230V)160A · 120m (230V)200A · 120m (230V)