Kabelarea för 700 Ampere vid 400 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 400 m vid 400V.
Copper Cable (≤3% Drop)3× 400 mm²Drop: 8.65V (2.16%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 42.8V (10.7%)
Voltage at Load391.4 VLine Loss: 10486.0 W
Max Power & Breaker484.97 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 6918.97 V (1729.74%) | 0.0 V | 11413.06 V (2853.27%) | 8388800.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 4151.38 V (1037.84%) | 0.0 V | 6847.84 V (1711.96%) | 5033280.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2594.61 V (648.65%) | 0.0 V | 4279.9 V (1069.97%) | 3145800.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1729.74 V (432.44%) | 0.0 V | 2853.27 V (713.32%) | 2097200.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 1037.84 V (259.46%) | 0.0 V | 1711.96 V (427.99%) | 1258320.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 648.65 V (162.16%) | 0.0 V | 1069.97 V (267.49%) | 786450.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 415.14 V (103.78%) | 0.0 V | 684.78 V (171.2%) | 503328.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 296.53 V (74.13%) | 103.5 V | 489.13 V (122.28%) | 359520.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 207.57 V (51.89%) | 192.4 V | 342.39 V (85.6%) | 251664.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 148.26 V (37.07%) | 251.7 V | 244.57 V (61.14%) | 179760.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 109.25 V (27.31%) | 290.8 V | 180.21 V (45.05%) | 132454.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 86.49 V (21.62%) | 313.5 V | 142.66 V (35.67%) | 104860.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 69.19 V (17.3%) | 330.8 V | 114.13 V (28.53%) | 83888.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 56.1 V (14.02%) | 343.9 V | 92.54 V (23.13%) | 68017.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 43.24 V (10.81%) | 356.8 V | 71.33 V (17.83%) | 52430.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 34.59 V (8.65%) | 365.4 V | 57.07 V (14.27%) | 41944.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 31458.0 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 400 Meter (400V)
Vilken kabelarea krävs för 700A vid 400 meter (400V)?
För 700 Ampere över 400 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (8.65V / 2.16%).
Hur stor effekt motsvarar 700A vid 400V?
Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (400V)
700A · 5m (400V)700A · 10m (400V)700A · 15m (400V)700A · 20m (400V)700A · 25m (400V)700A · 30m (400V)700A · 35m (400V)700A · 40m (400V)700A · 45m (400V)700A · 50m (400V)700A · 60m (400V)700A · 70m (400V)10A · 400m (400V)16A · 400m (400V)20A · 400m (400V)25A · 400m (400V)32A · 400m (400V)40A · 400m (400V)50A · 400m (400V)63A · 400m (400V)80A · 400m (400V)100A · 400m (400V)125A · 400m (400V)160A · 400m (400V)200A · 400m (400V)