Kabelarea för 700 Ampere vid 600 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 600 m vid 230V.
Copper Cable (≤3% Drop)7× 400 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 74.13V (32.23%)
Voltage at Load223.6 VLine Loss: 4494.0 W
Max Power & Breaker161.0 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 11984.0 V (5210.43%) | 0.0 V | 19768.0 V (8594.78%) | 8388800.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 7190.4 V (3126.26%) | 0.0 V | 11860.8 V (5156.87%) | 5033280.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 4494.0 V (1953.91%) | 0.0 V | 7413.0 V (3223.04%) | 3145800.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 2996.0 V (1302.61%) | 0.0 V | 4942.0 V (2148.7%) | 2097200.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 1797.6 V (781.57%) | 0.0 V | 2965.2 V (1289.22%) | 1258320.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 1123.5 V (488.48%) | 0.0 V | 1853.25 V (805.76%) | 786450.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 719.04 V (312.63%) | 0.0 V | 1186.08 V (515.69%) | 503328.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 513.6 V (223.3%) | 0.0 V | 847.2 V (368.35%) | 359520.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 359.52 V (156.31%) | 0.0 V | 593.04 V (257.84%) | 251664.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 256.8 V (111.65%) | 0.0 V | 423.6 V (184.17%) | 179760.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 189.22 V (82.27%) | 40.8 V | 312.13 V (135.71%) | 132454.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 149.8 V (65.13%) | 80.2 V | 247.1 V (107.43%) | 104860.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 119.84 V (52.1%) | 110.2 V | 197.68 V (85.95%) | 83888.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 97.17 V (42.25%) | 132.8 V | 160.28 V (69.69%) | 68017.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 74.9 V (32.57%) | 155.1 V | 123.55 V (53.72%) | 52430.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 41944.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 44.94 V (19.54%) | 185.1 V | 74.13 V (32.23%) | 31458.0 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 600 Meter (230V)
Vilken kabelarea krävs för 700A vid 600 meter (230V)?
För 700 Ampere över 600 meter vid 230V rekommenderas 7× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).
Hur stor effekt motsvarar 700A vid 230V?
Det motsvarar 161.0 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (230V)
700A · 5m (230V)700A · 10m (230V)700A · 15m (230V)700A · 20m (230V)700A · 25m (230V)700A · 30m (230V)700A · 35m (230V)700A · 40m (230V)700A · 45m (230V)700A · 50m (230V)700A · 60m (230V)700A · 70m (230V)10A · 600m (230V)16A · 600m (230V)20A · 600m (230V)25A · 600m (230V)32A · 600m (230V)40A · 600m (230V)50A · 600m (230V)63A · 600m (230V)80A · 600m (230V)100A · 600m (230V)125A · 600m (230V)160A · 600m (230V)200A · 600m (230V)