Kabelarea för 800 Ampere vid 200 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 200 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.42V (1.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.46V (6.11%)
Voltage at Load392.6 VLine Loss: 10272.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3953.69 V (988.42%)0.0 V6521.75 V (1630.44%)5478400.0 WDrop High
2.5 mm²24 A18 A2372.22 V (593.05%)0.0 V3913.05 V (978.26%)3287040.0 WDrop High
4 mm²32 A25 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)2054400.0 WDrop High
6 mm²41 A32 A988.42 V (247.11%)0.0 V1630.44 V (407.61%)1369600.0 WDrop High
10 mm²57 A44 A593.05 V (148.26%)0.0 V978.26 V (244.57%)821760.0 WDrop High
16 mm²76 A59 A370.66 V (92.66%)29.3 V611.41 V (152.85%)513600.0 WDrop High
25 mm²101 A78 A237.22 V (59.31%)162.8 V391.3 V (97.83%)328704.0 WDrop High
35 mm²125 A97 A169.44 V (42.36%)230.6 V279.5 V (69.88%)234788.6 WDrop High
50 mm²151 A118 A118.61 V (29.65%)281.4 V195.65 V (48.91%)164352.0 WDrop High
70 mm²192 A150 A84.72 V (21.18%)315.3 V139.75 V (34.94%)117394.3 WDrop High
95 mm²232 A181 A62.43 V (15.61%)337.6 V102.97 V (25.74%)86501.1 WDrop High
120 mm²269 A210 A49.42 V (12.36%)350.6 V81.52 V (20.38%)68480.0 WDrop High
150 mm²309 A241 A39.54 V (9.88%)360.5 V65.22 V (16.3%)54784.0 WDrop High
185 mm²353 A275 A32.06 V (8.01%)367.9 V52.88 V (13.22%)44419.5 WDrop High
240 mm²415 A324 A24.71 V (6.18%)375.3 V40.76 V (10.19%)34240.0 WDrop High
300 mm²477 A372 A19.77 V (4.94%)380.2 V32.61 V (8.15%)27392.0 WDrop High
400 mm²570 A445 A14.83 V (3.71%)385.2 V24.46 V (6.11%)20544.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 200 Meter (400V)

Vilken kabelarea krävs för 800A vid 200 meter (400V)?

För 800 Ampere över 200 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (7.42V / 1.85%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.