Kabelarea för 800 Ampere vid 600 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 600 m vid 400V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 73.37V (18.34%)
Voltage at Load388.9 VLine Loss: 15408.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11861.08 V (2965.27%)0.0 V19565.25 V (4891.31%)16435200.0 WDrop High
2.5 mm²24 A18 A7116.65 V (1779.16%)0.0 V11739.15 V (2934.79%)9861120.0 WDrop High
4 mm²32 A25 A4447.91 V (1111.98%)0.0 V7336.97 V (1834.24%)6163200.0 WDrop High
6 mm²41 A32 A2965.27 V (741.32%)0.0 V4891.31 V (1222.83%)4108800.0 WDrop High
10 mm²57 A44 A1779.16 V (444.79%)0.0 V2934.79 V (733.7%)2465280.0 WDrop High
16 mm²76 A59 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)1540800.0 WDrop High
25 mm²101 A78 A711.67 V (177.92%)0.0 V1173.91 V (293.48%)986112.0 WDrop High
35 mm²125 A97 A508.33 V (127.08%)0.0 V838.51 V (209.63%)704365.7 WDrop High
50 mm²151 A118 A355.83 V (88.96%)44.2 V586.96 V (146.74%)493056.0 WDrop High
70 mm²192 A150 A254.17 V (63.54%)145.8 V419.26 V (104.81%)352182.9 WDrop High
95 mm²232 A181 A187.28 V (46.82%)212.7 V308.92 V (77.23%)259503.2 WDrop High
120 mm²269 A210 A148.26 V (37.07%)251.7 V244.57 V (61.14%)205440.0 WDrop High
150 mm²309 A241 A118.61 V (29.65%)281.4 V195.65 V (48.91%)164352.0 WDrop High
185 mm²353 A275 A96.17 V (24.04%)303.8 V158.64 V (39.66%)133258.4 WDrop High
240 mm²415 A324 A74.13 V (18.53%)325.9 V122.28 V (30.57%)102720.0 WDrop High
300 mm²477 A372 A59.31 V (14.83%)340.7 V97.83 V (24.46%)82176.0 WDrop High
400 mm²570 A445 A44.48 V (11.12%)355.5 V73.37 V (18.34%)61632.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 600 Meter (400V)

Vilken kabelarea krävs för 800A vid 600 meter (400V)?

För 800 Ampere över 600 meter vid 400V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.