⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 90 Ampere vid 400 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 400 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.35V (2.76%)
Voltage at Load223.6 VLine Loss: 577.8 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)92448.0 WDrop High
2.5 mm²24 A18 A616.32 V (267.97%)0.0 V1016.64 V (442.02%)55468.8 WDrop High
4 mm²32 A25 A385.2 V (167.48%)0.0 V635.4 V (276.26%)34668.0 WDrop High
6 mm²41 A32 A256.8 V (111.65%)0.0 V423.6 V (184.17%)23112.0 WDrop High
10 mm²57 A44 A154.08 V (66.99%)75.9 V254.16 V (110.5%)13867.2 WDrop High
16 mm²76 A59 A96.3 V (41.87%)133.7 V158.85 V (69.07%)8667.0 WDrop High
25 mm²101 A78 A61.63 V (26.8%)168.4 V101.66 V (44.2%)5546.9 WDrop High
35 mm²125 A97 A44.02 V (19.14%)186.0 V72.62 V (31.57%)3962.1 WDrop High
50 mm²151 A118 A30.82 V (13.4%)199.2 V50.83 V (22.1%)2773.4 WDrop High
70 mm²192 A150 A22.01 V (9.57%)208.0 V36.31 V (15.79%)1981.0 WDrop High
95 mm²232 A181 A16.22 V (7.05%)213.8 V26.75 V (11.63%)1459.7 WDrop High
120 mm²269 A210 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1155.6 WDrop High
150 mm²309 A241 A10.27 V (4.47%)219.7 V16.94 V (7.37%)924.5 W~ ≤5%
185 mm²353 A275 A8.33 V (3.62%)221.7 V13.74 V (5.97%)749.6 W~ ≤5%
240 mm²415 A324 A6.42 V (2.79%)223.6 V10.59 V (4.6%)577.8 W✓ OK (≤3%)
300 mm²477 A372 A5.14 V (2.23%)224.9 V8.47 V (3.68%)462.2 W✓ OK (≤3%)
400 mm²570 A445 A3.85 V (1.67%)226.1 V6.35 V (2.76%)346.7 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 400 Meter (230V)

Vilken kabelarea krävs för 90A vid 400 meter (230V)?

För 90 Ampere över 400 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 90A vid 230V?

Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.