Kabelarea för 90 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 80 m vid 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 6.16V (2.68%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.35V (2.33%)
Voltage at Load223.8 VLine Loss: 554.7 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A205.44 V (89.32%)24.6 V338.88 V (147.34%)18489.6 WDrop High
2.5 mm²24 A18 A123.26 V (53.59%)106.7 V203.33 V (88.4%)11093.8 WDrop High
4 mm²32 A25 A77.04 V (33.5%)153.0 V127.08 V (55.25%)6933.6 WDrop High
6 mm²41 A32 A51.36 V (22.33%)178.6 V84.72 V (36.83%)4622.4 WDrop High
10 mm²57 A44 A30.82 V (13.4%)199.2 V50.83 V (22.1%)2773.4 WDrop High
16 mm²76 A59 A19.26 V (8.37%)210.7 V31.77 V (13.81%)1733.4 WDrop High
25 mm²101 A78 A12.33 V (5.36%)217.7 V20.33 V (8.84%)1109.4 WDrop High
35 mm²125 A97 A8.8 V (3.83%)221.2 V14.52 V (6.31%)792.4 W~ ≤5%
50 mm²151 A118 A6.16 V (2.68%)223.8 V10.17 V (4.42%)554.7 W✓ OK (≤3%)
70 mm²192 A150 A4.4 V (1.91%)225.6 V7.26 V (3.16%)396.2 W✓ OK (≤3%)
95 mm²232 A181 A3.24 V (1.41%)226.8 V5.35 V (2.33%)291.9 W✓ OK (≤3%)
120 mm²269 A210 A2.57 V (1.12%)227.4 V4.24 V (1.84%)231.1 W✓ OK (≤3%)
150 mm²309 A241 A2.05 V (0.89%)227.9 V3.39 V (1.47%)184.9 W✓ OK (≤3%)
185 mm²353 A275 A1.67 V (0.72%)228.3 V2.75 V (1.19%)149.9 W✓ OK (≤3%)
240 mm²415 A324 A1.28 V (0.56%)228.7 V2.12 V (0.92%)115.6 W✓ OK (≤3%)
300 mm²477 A372 A1.03 V (0.45%)229.0 V1.69 V (0.74%)92.4 W✓ OK (≤3%)
400 mm²570 A445 A0.77 V (0.33%)229.2 V1.27 V (0.55%)69.3 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 90A vid 80 meter (230V)?

För 90 Ampere över 80 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (6.16V / 2.68%).

Hur stor effekt motsvarar 90A vid 230V?

Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.