Kabelarea för 90 Ampere vid 80 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 80 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 10.67V (2.67%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 8.8V (2.2%)
Voltage at Load389.3 VLine Loss: 1664.1 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A177.92 V (44.48%)222.1 V293.48 V (73.37%)27734.4 WDrop High
2.5 mm²24 A18 A106.75 V (26.69%)293.3 V176.09 V (44.02%)16640.6 WDrop High
4 mm²32 A25 A66.72 V (16.68%)333.3 V110.05 V (27.51%)10400.4 WDrop High
6 mm²41 A32 A44.48 V (11.12%)355.5 V73.37 V (18.34%)6933.6 WDrop High
10 mm²57 A44 A26.69 V (6.67%)373.3 V44.02 V (11.01%)4160.2 WDrop High
16 mm²76 A59 A16.68 V (4.17%)383.3 V27.51 V (6.88%)2600.1 WDrop High
25 mm²101 A78 A10.67 V (2.67%)389.3 V17.61 V (4.4%)1664.1 W✓ OK (≤3%)
35 mm²125 A97 A7.62 V (1.91%)392.4 V12.58 V (3.14%)1188.6 W✓ OK (≤3%)
50 mm²151 A118 A5.34 V (1.33%)394.7 V8.8 V (2.2%)832.0 W✓ OK (≤3%)
70 mm²192 A150 A3.81 V (0.95%)396.2 V6.29 V (1.57%)594.3 W✓ OK (≤3%)
95 mm²232 A181 A2.81 V (0.7%)397.2 V4.63 V (1.16%)437.9 W✓ OK (≤3%)
120 mm²269 A210 A2.22 V (0.56%)397.8 V3.67 V (0.92%)346.7 W✓ OK (≤3%)
150 mm²309 A241 A1.78 V (0.44%)398.2 V2.93 V (0.73%)277.3 W✓ OK (≤3%)
185 mm²353 A275 A1.44 V (0.36%)398.6 V2.38 V (0.59%)224.9 W✓ OK (≤3%)
240 mm²415 A324 A1.11 V (0.28%)398.9 V1.83 V (0.46%)173.3 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (0.22%)399.1 V1.47 V (0.37%)138.7 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (0.17%)399.3 V1.1 V (0.28%)104.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 80 Meter (400V)

Vilken kabelarea krävs för 90A vid 80 meter (400V)?

För 90 Ampere över 80 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (10.67V / 2.67%).

Hur stor effekt motsvarar 90A vid 400V?

Det motsvarar 62.35 kW med en rekommenderad säkring på 90A.