⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)8 AWGDrop: 10.02V (2.09%)
Voltage at Load End470.3 VLoss: 9.67 V (167.4 W)
Power & Breaker (125%)8.31 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A24.44 V (5.09%)455.6 V40.32 V (8.4%)423.3 WDrop/Amp High
12 AWG3.31 mm²20 A15.36 V (3.2%)464.6 V25.34 V (5.28%)266.0 W~ ≤5%
10 AWG5.26 mm²30 A9.67 V (2.01%)470.3 V15.94 V (3.32%)167.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A6.07 V (1.27%)473.9 V10.02 V (2.09%)105.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.82 V (0.8%)476.2 V6.31 V (1.31%)66.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.4 V (0.5%)477.6 V3.97 V (0.83%)41.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.91 V (0.4%)478.1 V3.14 V (0.66%)33.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.51 V (0.32%)478.5 V2.49 V (0.52%)26.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.2 V (0.25%)478.8 V1.98 V (0.41%)20.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.95 V (0.2%)479.0 V1.57 V (0.33%)16.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.75 V (0.16%)479.2 V1.24 V (0.26%)13.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.6 V (0.12%)479.4 V0.99 V (0.21%)10.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.47 V (0.1%)479.5 V0.78 V (0.16%)8.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.4 V (0.08%)479.6 V0.66 V (0.14%)7.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.33 V (0.07%)479.7 V0.55 V (0.11%)5.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.29 V (0.06%)479.7 V0.47 V (0.1%)5.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.25 V (0.05%)479.7 V0.41 V (0.09%)4.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.2 V (0.04%)479.8 V0.33 V (0.07%)3.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.17 V (0.03%)479.8 V0.28 V (0.06%)2.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.03%)479.9 V0.22 V (0.05%)2.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.02%)479.9 V0.17 V (0.03%)1.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 450 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 9.67V (2.01%) and delivers 470.3V at the load.

What size aluminum wire is required for 10 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 10.02V (2.09%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.