⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.04%
Aluminum Wire (≤3% Drop)1 AWGDrop: 4.39V (2.11%)
Voltage at Load End203.8 VLoss: 4.24 V (733.7 W)
Power & Breaker (125%)36.03 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.32 V (26.11%)153.7 V89.6 V (43.07%)9407.8 WDrop/Amp High
12 AWG3.31 mm²20 A34.13 V (16.41%)173.9 V56.3 V (27.07%)5911.8 WDrop/Amp High
10 AWG5.26 mm²30 A21.48 V (10.33%)186.5 V35.43 V (17.03%)3720.2 WDrop/Amp High
8 AWG8.37 mm²50 A13.5 V (6.49%)194.5 V22.27 V (10.7%)2337.9 WDrop/Amp High
6 AWG13.3 mm²65 A8.49 V (4.08%)199.5 V14.01 V (6.74%)1471.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.34 V (2.57%)202.7 V8.81 V (4.24%)925.2 WDrop/Amp High
3 AWG26.67 mm²100 A4.24 V (2.04%)203.8 V6.99 V (3.36%)733.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.36 V (1.62%)204.6 V5.54 V (2.66%)582.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.66 V (1.28%)205.3 V4.39 V (2.11%)461.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.11 V (1.02%)205.9 V3.48 V (1.67%)365.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.68 V (0.81%)206.3 V2.76 V (1.33%)290.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.33 V (0.64%)206.7 V2.19 V (1.05%)230.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.05 V (0.51%)206.9 V1.74 V (0.84%)182.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.89 V (0.43%)207.1 V1.47 V (0.71%)154.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.74 V (0.36%)207.3 V1.23 V (0.59%)128.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.64 V (0.31%)207.4 V1.05 V (0.51%)110.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.27%)207.4 V0.92 V (0.44%)96.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.21%)207.6 V0.74 V (0.35%)77.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.37 V (0.18%)207.6 V0.61 V (0.29%)64.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.14%)207.7 V0.49 V (0.24%)51.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.22 V (0.11%)207.8 V0.37 V (0.18%)38.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 100 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 4.24V (2.04%) and delivers 203.8V at the load.

What size aluminum wire is required for 100 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 4.39V (2.11%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.