⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 1.52%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 3.29V (1.58%)
Voltage at Load End204.8 VLoss: 3.17 V (823.1 W)
Power & Breaker (125%)54.04 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A81.47 V (39.17%)126.5 V134.39 V (64.61%)21167.5 WDrop/Amp High
12 AWG3.31 mm²20 A51.2 V (24.61%)156.8 V84.45 V (40.6%)13301.6 WDrop/Amp High
10 AWG5.26 mm²30 A32.22 V (15.49%)175.8 V53.14 V (25.55%)8370.4 WDrop/Amp High
8 AWG8.37 mm²50 A20.25 V (9.73%)187.8 V33.4 V (16.06%)5260.3 WDrop/Amp High
6 AWG13.3 mm²65 A12.74 V (6.13%)195.3 V21.02 V (10.1%)3310.4 WDrop/Amp High
4 AWG21.15 mm²85 A8.01 V (3.85%)200.0 V13.22 V (6.35%)2081.7 WDrop/Amp High
3 AWG26.67 mm²100 A6.35 V (3.05%)201.6 V10.48 V (5.04%)1650.9 WDrop/Amp High
2 AWG33.62 mm²115 A5.04 V (2.42%)203.0 V8.31 V (4.0%)1309.6 WDrop/Amp High
1 AWG42.41 mm²130 A4.0 V (1.92%)204.0 V6.59 V (3.17%)1038.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.17 V (1.52%)204.8 V5.23 V (2.51%)823.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.51 V (1.21%)205.5 V4.15 V (1.99%)652.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.99 V (0.96%)206.0 V3.29 V (1.58%)517.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.58 V (0.76%)206.4 V2.61 V (1.25%)410.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.34 V (0.64%)206.7 V2.21 V (1.06%)347.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.11 V (0.54%)206.9 V1.84 V (0.88%)289.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.96 V (0.46%)207.0 V1.58 V (0.76%)248.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.84 V (0.4%)207.2 V1.38 V (0.66%)217.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.67 V (0.32%)207.3 V1.1 V (0.53%)173.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.56 V (0.27%)207.4 V0.92 V (0.44%)144.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.45 V (0.21%)207.6 V0.74 V (0.35%)115.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.33 V (0.16%)207.7 V0.55 V (0.27%)86.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 100 feet one-way at 208V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 3.17V (1.52%) and delivers 204.8V at the load.

What size aluminum wire is required for 150 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 3.29V (1.58%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.