⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.19V (2.65%)
Voltage at Load End116.5 VLoss: 3.45 V (345.3 W)
Power & Breaker (125%)12.0 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.12 V (117.6%)0.0 V232.78 V (193.98%)14111.7 WDrop/Amp High
12 AWG3.31 mm²20 A88.68 V (73.9%)31.3 V146.28 V (121.9%)8867.7 WDrop/Amp High
10 AWG5.26 mm²30 A55.8 V (46.5%)64.2 V92.05 V (76.71%)5580.3 WDrop/Amp High
8 AWG8.37 mm²50 A35.07 V (29.22%)84.9 V57.85 V (48.21%)3506.8 WDrop/Amp High
6 AWG13.3 mm²65 A22.07 V (18.39%)97.9 V36.4 V (30.34%)2206.9 WDrop/Amp High
4 AWG21.15 mm²85 A13.88 V (11.57%)106.1 V22.89 V (19.08%)1387.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (9.17%)109.0 V18.15 V (15.13%)1100.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.73 V (7.28%)111.3 V14.4 V (12.0%)873.1 WDrop/Amp High
1 AWG42.41 mm²130 A6.92 V (5.77%)113.1 V11.42 V (9.51%)692.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (4.57%)114.5 V9.05 V (7.54%)548.7 W~ ≤5%
2/0 AWG67.43 mm²175 A4.35 V (3.63%)115.6 V7.18 V (5.98%)435.3 W~ ≤5%
3/0 AWG85.01 mm²200 A3.45 V (2.88%)116.5 V5.7 V (4.75%)345.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.74 V (2.28%)117.3 V4.52 V (3.76%)273.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.32 V (1.93%)117.7 V3.82 V (3.18%)231.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.93 V (1.61%)118.1 V3.19 V (2.65%)193.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.66 V (1.38%)118.3 V2.73 V (2.28%)165.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.45 V (1.21%)118.6 V2.39 V (1.99%)144.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.16 V (0.97%)118.8 V1.91 V (1.59%)115.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.97 V (0.8%)119.0 V1.59 V (1.33%)96.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.77 V (0.64%)119.2 V1.27 V (1.06%)77.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.58 V (0.48%)119.4 V0.96 V (0.8%)57.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 225 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.45V (2.88%) and delivers 116.5V at the load.

What size aluminum wire is required for 100 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.19V (2.65%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.