⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.59V (2.99%)
Voltage at Load End116.5 VLoss: 3.46 V (173.0 W)
Power & Breaker (125%)6.0 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A70.56 V (58.8%)49.4 V116.39 V (96.99%)3527.9 WDrop/Amp High
12 AWG3.31 mm²20 A44.34 V (36.95%)75.7 V73.14 V (60.95%)2216.9 WDrop/Amp High
10 AWG5.26 mm²30 A27.9 V (23.25%)92.1 V46.02 V (38.35%)1395.1 WDrop/Amp High
8 AWG8.37 mm²50 A17.53 V (14.61%)102.5 V28.92 V (24.1%)876.7 WDrop/Amp High
6 AWG13.3 mm²65 A11.03 V (9.2%)109.0 V18.2 V (15.17%)551.7 WDrop/Amp High
4 AWG21.15 mm²85 A6.94 V (5.78%)113.1 V11.45 V (9.54%)347.0 WDrop/Amp High
3 AWG26.67 mm²100 A5.5 V (4.59%)114.5 V9.08 V (7.56%)275.1 W~ ≤5%
2 AWG33.62 mm²115 A4.37 V (3.64%)115.6 V7.2 V (6.0%)218.3 W~ ≤5%
1 AWG42.41 mm²130 A3.46 V (2.88%)116.5 V5.71 V (4.76%)173.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.74 V (2.29%)117.3 V4.53 V (3.77%)137.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.18 V (1.81%)117.8 V3.59 V (2.99%)108.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.73 V (1.44%)118.3 V2.85 V (2.37%)86.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.37 V (1.14%)118.6 V2.26 V (1.88%)68.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.16 V (0.97%)118.8 V1.91 V (1.59%)57.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.97 V (0.8%)119.0 V1.59 V (1.33%)48.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.83 V (0.69%)119.2 V1.37 V (1.14%)41.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.72 V (0.6%)119.3 V1.19 V (1.0%)36.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.58 V (0.48%)119.4 V0.96 V (0.8%)29.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.48 V (0.4%)119.5 V0.8 V (0.66%)24.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.39 V (0.32%)119.6 V0.64 V (0.53%)19.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.29 V (0.24%)119.7 V0.48 V (0.4%)14.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 225 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 3.46V (2.88%) and delivers 116.5V at the load.

What size aluminum wire is required for 50 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.59V (2.99%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.