🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.43V (2.86%)
Voltage at Load End116.7 VLoss: 3.31 V (49.7 W)
Power & Breaker (125%)1.8 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.17 V (17.64%)98.8 V34.92 V (29.1%)317.5 WDrop/Amp High
12 AWG3.31 mm²20 A13.3 V (11.08%)106.7 V21.94 V (18.28%)199.5 WDrop/Amp High
10 AWG5.26 mm²30 A8.37 V (6.98%)111.6 V13.81 V (11.51%)125.6 WDrop/Amp High
8 AWG8.37 mm²50 A5.26 V (4.38%)114.7 V8.68 V (7.23%)78.9 W~ ≤5%
6 AWG13.3 mm²65 A3.31 V (2.76%)116.7 V5.46 V (4.55%)49.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.08 V (1.73%)117.9 V3.43 V (2.86%)31.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.65 V (1.38%)118.3 V2.72 V (2.27%)24.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.31 V (1.09%)118.7 V2.16 V (1.8%)19.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.04 V (0.87%)119.0 V1.71 V (1.43%)15.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.82 V (0.69%)119.2 V1.36 V (1.13%)12.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.65 V (0.54%)119.3 V1.08 V (0.9%)9.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.52 V (0.43%)119.5 V0.85 V (0.71%)7.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.41 V (0.34%)119.6 V0.68 V (0.56%)6.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.35 V (0.29%)119.7 V0.57 V (0.48%)5.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.29 V (0.24%)119.7 V0.48 V (0.4%)4.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.25 V (0.21%)119.8 V0.41 V (0.34%)3.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.22 V (0.18%)119.8 V0.36 V (0.3%)3.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.17 V (0.14%)119.8 V0.29 V (0.24%)2.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.12%)119.9 V0.24 V (0.2%)2.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.1%)119.9 V0.19 V (0.16%)1.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.07%)119.9 V0.14 V (0.12%)1.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 225 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.31V (2.76%) and delivers 116.7V at the load.

What size aluminum wire is required for 15 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.43V (2.86%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.