🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)1 AWGDrop: 3.42V (2.85%)
Voltage at Load End116.7 VLoss: 3.3 V (99.1 W)
Power & Breaker (125%)3.6 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A42.33 V (35.28%)77.7 V69.83 V (58.19%)1270.0 WDrop/Amp High
12 AWG3.31 mm²20 A26.6 V (22.17%)93.4 V43.88 V (36.57%)798.1 WDrop/Amp High
10 AWG5.26 mm²30 A16.74 V (13.95%)103.3 V27.61 V (23.01%)502.2 WDrop/Amp High
8 AWG8.37 mm²50 A10.52 V (8.77%)109.5 V17.35 V (14.46%)315.6 WDrop/Amp High
6 AWG13.3 mm²65 A6.62 V (5.52%)113.4 V10.92 V (9.1%)198.6 WDrop/Amp High
4 AWG21.15 mm²85 A4.16 V (3.47%)115.8 V6.87 V (5.72%)124.9 W~ ≤5%
3 AWG26.67 mm²100 A3.3 V (2.75%)116.7 V5.45 V (4.54%)99.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.62 V (2.18%)117.4 V4.32 V (3.6%)78.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.08 V (1.73%)117.9 V3.42 V (2.85%)62.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.65 V (1.37%)118.4 V2.72 V (2.26%)49.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.31 V (1.09%)118.7 V2.15 V (1.8%)39.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.04 V (0.86%)119.0 V1.71 V (1.42%)31.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.82 V (0.68%)119.2 V1.35 V (1.13%)24.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.7 V (0.58%)119.3 V1.15 V (0.96%)20.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.58 V (0.48%)119.4 V0.96 V (0.8%)17.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.5 V (0.41%)119.5 V0.82 V (0.68%)14.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.43 V (0.36%)119.6 V0.72 V (0.6%)13.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.35 V (0.29%)119.7 V0.57 V (0.48%)10.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.29 V (0.24%)119.7 V0.48 V (0.4%)8.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.23 V (0.19%)119.8 V0.38 V (0.32%)7.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.14%)119.8 V0.29 V (0.24%)5.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 225 feet one-way at 120V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 3.3V (2.75%) and delivers 116.7V at the load.

What size aluminum wire is required for 30 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 3.42V (2.85%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.