🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.55V (21.23%)
Voltage at Load End11.7 VLoss: 0.31 V (30.9 W)
Power & Breaker (125%)1.2 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A376.31 V (3135.92%)0.0 V620.74 V (5172.81%)37631.1 WDrop/Amp High
12 AWG3.31 mm²20 A236.47 V (1970.61%)0.0 V390.07 V (3250.59%)23647.3 WDrop/Amp High
10 AWG5.26 mm²30 A148.81 V (1240.06%)0.0 V245.46 V (2045.52%)14880.7 WDrop/Amp High
8 AWG8.37 mm²50 A93.52 V (779.3%)0.0 V154.26 V (1285.48%)9351.6 WDrop/Amp High
6 AWG13.3 mm²65 A58.85 V (490.43%)0.0 V97.08 V (808.98%)5885.2 WDrop/Amp High
4 AWG21.15 mm²85 A37.01 V (308.4%)0.0 V61.05 V (508.72%)3700.8 WDrop/Amp High
3 AWG26.67 mm²100 A29.35 V (244.57%)0.0 V48.41 V (403.43%)2934.9 WDrop/Amp High
2 AWG33.62 mm²115 A23.28 V (194.01%)0.0 V38.4 V (320.03%)2328.2 WDrop/Amp High
1 AWG42.41 mm²130 A18.46 V (153.8%)0.0 V30.44 V (253.7%)1845.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.63 V (121.94%)0.0 V24.14 V (201.15%)1463.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.61 V (96.73%)0.4 V19.15 V (159.56%)1160.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.21 V (76.73%)2.8 V15.19 V (126.57%)920.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.3 V (60.85%)4.7 V12.04 V (100.37%)730.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.18 V (51.48%)5.8 V10.19 V (84.92%)617.8 WDrop/Amp High
300 kcmil152.0 mm²285 A5.15 V (42.91%)6.9 V8.49 V (70.79%)515.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.41 V (36.79%)7.6 V7.28 V (60.68%)441.5 WDrop/Amp High
400 kcmil202.7 mm²335 A3.86 V (32.18%)8.1 V6.37 V (53.08%)386.2 WDrop/Amp High
500 kcmil253.4 mm²380 A3.09 V (25.74%)8.9 V5.1 V (42.46%)308.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.57 V (21.46%)9.4 V4.25 V (35.39%)257.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.06 V (17.17%)9.9 V3.4 V (28.31%)206.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.54 V (12.87%)10.5 V2.55 V (21.23%)154.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 600 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 100 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.55V (21.23%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.