🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.58%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.02V (8.49%)
Voltage at Load End11.7 VLoss: 0.31 V (12.3 W)
Power & Breaker (125%)0.48 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A150.52 V (1254.37%)0.0 V248.29 V (2069.12%)6021.0 WDrop/Amp High
12 AWG3.31 mm²20 A94.59 V (788.24%)0.0 V156.03 V (1300.23%)3783.6 WDrop/Amp High
10 AWG5.26 mm²30 A59.52 V (496.02%)0.0 V98.19 V (818.21%)2380.9 WDrop/Amp High
8 AWG8.37 mm²50 A37.41 V (311.72%)0.0 V61.7 V (514.19%)1496.3 WDrop/Amp High
6 AWG13.3 mm²65 A23.54 V (196.17%)0.0 V38.83 V (323.59%)941.6 WDrop/Amp High
4 AWG21.15 mm²85 A14.8 V (123.36%)0.0 V24.42 V (203.49%)592.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.74 V (97.83%)0.3 V19.36 V (161.37%)469.6 WDrop/Amp High
2 AWG33.62 mm²115 A9.31 V (77.61%)2.7 V15.36 V (128.01%)372.5 WDrop/Amp High
1 AWG42.41 mm²130 A7.38 V (61.52%)4.6 V12.18 V (101.48%)295.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.85 V (48.78%)6.1 V9.66 V (80.46%)234.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.64 V (38.69%)7.4 V7.66 V (63.83%)185.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.68 V (30.69%)8.3 V6.08 V (50.63%)147.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.92 V (24.34%)9.1 V4.82 V (40.15%)116.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.47 V (20.59%)9.5 V4.08 V (33.97%)98.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.06 V (17.17%)9.9 V3.4 V (28.31%)82.4 WDrop/Amp High
350 kcmil177.3 mm²310 A1.77 V (14.72%)10.2 V2.91 V (24.27%)70.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.54 V (12.87%)10.5 V2.55 V (21.23%)61.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.24 V (10.3%)10.8 V2.04 V (16.98%)49.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.03 V (8.58%)11.0 V1.7 V (14.16%)41.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.82 V (6.87%)11.2 V1.36 V (11.33%)33.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.62 V (5.15%)11.4 V1.02 V (8.49%)24.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 600 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.58%) and delivers 11.7V at the load.

What size aluminum wire is required for 40 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.02V (8.49%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.