⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.19V (26.54%)
Voltage at Load End11.7 VLoss: 0.32 V (40.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A470.39 V (3919.9%)0.0 V775.92 V (6466.01%)58798.6 WDrop/Amp High
12 AWG3.31 mm²20 A295.59 V (2463.26%)0.0 V487.59 V (4063.23%)36948.9 WDrop/Amp High
10 AWG5.26 mm²30 A186.01 V (1550.08%)0.0 V306.83 V (2556.9%)23251.1 WDrop/Amp High
8 AWG8.37 mm²50 A116.89 V (974.12%)0.0 V192.82 V (1606.85%)14611.8 WDrop/Amp High
6 AWG13.3 mm²65 A73.56 V (613.04%)0.0 V121.35 V (1011.23%)9195.6 WDrop/Amp High
4 AWG21.15 mm²85 A46.26 V (385.5%)0.0 V76.31 V (635.9%)5782.6 WDrop/Amp High
3 AWG26.67 mm²100 A36.69 V (305.71%)0.0 V60.51 V (504.29%)4585.7 WDrop/Amp High
2 AWG33.62 mm²115 A29.1 V (242.52%)0.0 V48.0 V (400.04%)3637.7 WDrop/Amp High
1 AWG42.41 mm²130 A23.07 V (192.25%)0.0 V38.06 V (317.13%)2883.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.29 V (152.43%)0.0 V30.17 V (251.44%)2286.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.51 V (120.92%)0.0 V23.93 V (199.46%)1813.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.51 V (95.91%)0.5 V18.99 V (158.21%)1438.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.13 V (76.06%)2.9 V15.06 V (125.46%)1140.9 WDrop/Amp High
250 kcmil126.7 mm²255 A7.72 V (64.35%)4.3 V12.74 V (106.15%)965.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.44 V (53.64%)5.6 V10.62 V (88.48%)804.6 WDrop/Amp High
350 kcmil177.3 mm²310 A5.52 V (45.99%)6.5 V9.1 V (75.86%)689.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.83 V (40.22%)7.2 V7.96 V (66.35%)603.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.86 V (32.18%)8.1 V6.37 V (53.08%)482.6 WDrop/Amp High
600 kcmil304.0 mm²420 A3.22 V (26.82%)8.8 V5.31 V (44.24%)402.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.57 V (21.46%)9.4 V4.25 V (35.39%)321.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.93 V (16.09%)10.1 V3.19 V (26.54%)241.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 600 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.19V (26.54%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.