⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 36.78V (17.68%)
Voltage at Load End202.4 VLoss: 5.58 V (9654.7 W)
Power & Breaker (125%)360.27 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5431.58 V (2611.34%)0.0 V8959.57 V (4307.48%)9407769.2 WDrop/Amp High
12 AWG3.31 mm²20 A3413.2 V (1640.96%)0.0 V5630.18 V (2706.82%)5911830.8 WDrop/Amp High
10 AWG5.26 mm²30 A2147.85 V (1032.62%)0.0 V3542.95 V (1703.34%)3720182.5 WDrop/Amp High
8 AWG8.37 mm²50 A1349.78 V (648.93%)0.0 V2226.51 V (1070.44%)2337892.5 WDrop/Amp High
6 AWG13.3 mm²65 A849.45 V (408.39%)0.0 V1401.2 V (673.65%)1471290.2 WDrop/Amp High
4 AWG21.15 mm²85 A534.17 V (256.81%)0.0 V881.13 V (423.62%)925208.5 WDrop/Amp High
3 AWG26.67 mm²100 A423.61 V (203.66%)0.0 V698.76 V (335.94%)733714.3 WDrop/Amp High
2 AWG33.62 mm²115 A336.04 V (161.56%)0.0 V554.31 V (266.5%)582039.3 WDrop/Amp High
1 AWG42.41 mm²130 A266.39 V (128.07%)0.0 V439.42 V (211.26%)461404.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A211.21 V (101.54%)0.0 V348.4 V (167.5%)365828.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A167.55 V (80.55%)40.5 V276.37 V (132.87%)290199.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A132.9 V (63.89%)75.1 V219.22 V (105.39%)230186.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A105.39 V (50.67%)102.6 V173.84 V (83.58%)182538.8 WDrop/Amp High
250 kcmil126.7 mm²255 A89.17 V (42.87%)118.8 V147.09 V (70.71%)154444.8 WDrop/Amp High
300 kcmil152.0 mm²285 A74.33 V (35.73%)133.7 V122.6 V (58.94%)128737.9 WDrop/Amp High
350 kcmil177.3 mm²310 A63.72 V (30.63%)144.3 V105.11 V (50.53%)110367.5 WDrop/Amp High
400 kcmil202.7 mm²335 A55.74 V (26.8%)152.3 V91.94 V (44.2%)96537.5 WDrop/Amp High
500 kcmil253.4 mm²380 A44.58 V (21.43%)163.4 V73.54 V (35.36%)77222.4 WDrop/Amp High
600 kcmil304.0 mm²420 A37.16 V (17.87%)170.8 V61.3 V (29.47%)64368.9 WDrop/Amp High
750 kcmil380.0 mm²475 A29.73 V (14.29%)178.3 V49.04 V (23.58%)51495.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A22.3 V (10.72%)185.7 V36.78 V (17.68%)38618.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 1000 feet one-way at 208V (3-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.58V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 1000 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 36.78V (17.68%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.