⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.36V (3.06%)
Voltage at Load End237.8 VLoss: 2.23 V (3861.9 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1086.32 V (452.63%)0.0 V1791.91 V (746.63%)1881553.8 WDrop/Amp High
12 AWG3.31 mm²20 A682.64 V (284.43%)0.0 V1126.04 V (469.18%)1182366.2 WDrop/Amp High
10 AWG5.26 mm²30 A429.57 V (178.99%)0.0 V708.59 V (295.25%)744036.5 WDrop/Amp High
8 AWG8.37 mm²50 A269.96 V (112.48%)0.0 V445.3 V (185.54%)467578.5 WDrop/Amp High
6 AWG13.3 mm²65 A169.89 V (70.79%)70.1 V280.24 V (116.77%)294258.0 WDrop/Amp High
4 AWG21.15 mm²85 A106.83 V (44.51%)133.2 V176.23 V (73.43%)185041.7 WDrop/Amp High
3 AWG26.67 mm²100 A84.72 V (35.3%)155.3 V139.75 V (58.23%)146742.9 WDrop/Amp High
2 AWG33.62 mm²115 A67.21 V (28.0%)172.8 V110.86 V (46.19%)116407.9 WDrop/Amp High
1 AWG42.41 mm²130 A53.28 V (22.2%)186.7 V87.88 V (36.62%)92280.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A42.24 V (17.6%)197.8 V69.68 V (29.03%)73165.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A33.51 V (13.96%)206.5 V55.27 V (23.03%)58039.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A26.58 V (11.07%)213.4 V43.84 V (18.27%)46037.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.08 V (8.78%)218.9 V34.77 V (14.49%)36507.8 WDrop/Amp High
250 kcmil126.7 mm²255 A17.83 V (7.43%)222.2 V29.42 V (12.26%)30889.0 WDrop/Amp High
300 kcmil152.0 mm²285 A14.87 V (6.19%)225.1 V24.52 V (10.22%)25747.6 WDrop/Amp High
350 kcmil177.3 mm²310 A12.74 V (5.31%)227.3 V21.02 V (8.76%)22073.5 WDrop/Amp High
400 kcmil202.7 mm²335 A11.15 V (4.64%)228.9 V18.39 V (7.66%)19307.5 WDrop/Amp High
500 kcmil253.4 mm²380 A8.92 V (3.72%)231.1 V14.71 V (6.13%)15444.5 WDrop/Amp High
600 kcmil304.0 mm²420 A7.43 V (3.1%)232.6 V12.26 V (5.11%)12873.8 WDrop/Amp High
750 kcmil380.0 mm²475 A5.95 V (2.48%)234.1 V9.81 V (4.09%)10299.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.46 V (1.86%)235.5 V7.36 V (3.06%)7723.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 200 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.23V (0.93%) and delivers 237.8V at the load.

What size aluminum wire is required for 1000 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.36V (3.06%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.