🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.55V (6.9%)
Voltage at Load End235.0 VLoss: 5.01 V (8689.2 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2444.21 V (1018.42%)0.0 V4031.8 V (1679.92%)4233496.2 WDrop/Amp High
12 AWG3.31 mm²20 A1535.94 V (639.97%)0.0 V2533.58 V (1055.66%)2660323.9 WDrop/Amp High
10 AWG5.26 mm²30 A966.53 V (402.72%)0.0 V1594.33 V (664.3%)1674082.1 WDrop/Amp High
8 AWG8.37 mm²50 A607.4 V (253.08%)0.0 V1001.93 V (417.47%)1052051.6 WDrop/Amp High
6 AWG13.3 mm²65 A382.25 V (159.27%)0.0 V630.54 V (262.72%)662080.6 WDrop/Amp High
4 AWG21.15 mm²85 A240.38 V (100.16%)0.0 V396.51 V (165.21%)416343.8 WDrop/Amp High
3 AWG26.67 mm²100 A190.62 V (79.43%)49.4 V314.44 V (131.02%)330171.4 WDrop/Amp High
2 AWG33.62 mm²115 A151.22 V (63.01%)88.8 V249.44 V (103.93%)261917.7 WDrop/Amp High
1 AWG42.41 mm²130 A119.88 V (49.95%)120.1 V197.74 V (82.39%)207632.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A95.05 V (39.6%)145.0 V156.78 V (65.32%)164622.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A75.4 V (31.42%)164.6 V124.37 V (51.82%)130589.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A59.8 V (24.92%)180.2 V98.65 V (41.1%)103584.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A47.42 V (19.76%)192.6 V78.23 V (32.6%)82142.5 WDrop/Amp High
250 kcmil126.7 mm²255 A40.13 V (16.72%)199.9 V66.19 V (27.58%)69500.2 WDrop/Amp High
300 kcmil152.0 mm²285 A33.45 V (13.94%)206.6 V55.17 V (22.99%)57932.1 WDrop/Amp High
350 kcmil177.3 mm²310 A28.67 V (11.95%)211.3 V47.3 V (19.71%)49665.4 WDrop/Amp High
400 kcmil202.7 mm²335 A25.08 V (10.45%)214.9 V41.37 V (17.24%)43441.9 WDrop/Amp High
500 kcmil253.4 mm²380 A20.06 V (8.36%)219.9 V33.09 V (13.79%)34750.1 WDrop/Amp High
600 kcmil304.0 mm²420 A16.72 V (6.97%)223.3 V27.59 V (11.49%)28966.0 WDrop/Amp High
750 kcmil380.0 mm²475 A13.38 V (5.57%)226.6 V22.07 V (9.2%)23172.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.03 V (4.18%)230.0 V16.55 V (6.9%)17378.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 450 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.01V (2.09%) and delivers 235.0V at the load.

What size aluminum wire is required for 1000 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.55V (6.9%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.