🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.07V (9.19%)
Voltage at Load End233.3 VLoss: 6.69 V (11585.6 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3258.95 V (1357.89%)0.0 V5375.74 V (2239.89%)5644661.5 WDrop/Amp High
12 AWG3.31 mm²20 A2047.92 V (853.3%)0.0 V3378.11 V (1407.55%)3547098.5 WDrop/Amp High
10 AWG5.26 mm²30 A1288.71 V (536.96%)0.0 V2125.77 V (885.74%)2232109.5 WDrop/Amp High
8 AWG8.37 mm²50 A809.87 V (337.45%)0.0 V1335.91 V (556.63%)1402735.5 WDrop/Amp High
6 AWG13.3 mm²65 A509.67 V (212.36%)0.0 V840.72 V (350.3%)882774.1 WDrop/Amp High
4 AWG21.15 mm²85 A320.5 V (133.54%)0.0 V528.68 V (220.28%)555125.1 WDrop/Amp High
3 AWG26.67 mm²100 A254.17 V (105.9%)0.0 V419.26 V (174.69%)440228.6 WDrop/Amp High
2 AWG33.62 mm²115 A201.62 V (84.01%)38.4 V332.59 V (138.58%)349223.6 WDrop/Amp High
1 AWG42.41 mm²130 A159.84 V (66.6%)80.2 V263.65 V (109.86%)276842.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A126.73 V (52.8%)113.3 V209.04 V (87.1%)219497.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A100.53 V (41.89%)139.5 V165.82 V (69.09%)174119.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A79.74 V (33.22%)160.3 V131.53 V (54.81%)138111.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.23 V (26.35%)176.8 V104.31 V (43.46%)109523.3 WDrop/Amp High
250 kcmil126.7 mm²255 A53.5 V (22.29%)186.5 V88.25 V (36.77%)92666.9 WDrop/Amp High
300 kcmil152.0 mm²285 A44.6 V (18.58%)195.4 V73.56 V (30.65%)77242.7 WDrop/Amp High
350 kcmil177.3 mm²310 A38.23 V (15.93%)201.8 V63.07 V (26.28%)66220.5 WDrop/Amp High
400 kcmil202.7 mm²335 A33.44 V (13.93%)206.6 V55.16 V (22.98%)57922.5 WDrop/Amp High
500 kcmil253.4 mm²380 A26.75 V (11.15%)213.2 V44.13 V (18.39%)46333.4 WDrop/Amp High
600 kcmil304.0 mm²420 A22.3 V (9.29%)217.7 V36.78 V (15.33%)38621.4 WDrop/Amp High
750 kcmil380.0 mm²475 A17.84 V (7.43%)222.2 V29.43 V (12.26%)30897.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.38 V (5.57%)226.6 V22.07 V (9.19%)23171.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 600 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 1000 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.07V (9.19%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.