🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 29.42V (14.15%)
Voltage at Load End202.1 VLoss: 5.95 V (10298.4 W)
Power & Breaker (125%)360.27 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4345.26 V (2089.07%)0.0 V7167.65 V (3445.99%)7526215.4 WDrop/Amp High
12 AWG3.31 mm²20 A2730.56 V (1312.77%)0.0 V4504.14 V (2165.45%)4729464.7 WDrop/Amp High
10 AWG5.26 mm²30 A1718.28 V (826.1%)0.0 V2834.36 V (1362.67%)2976146.0 WDrop/Amp High
8 AWG8.37 mm²50 A1079.83 V (519.15%)0.0 V1781.21 V (856.35%)1870314.0 WDrop/Amp High
6 AWG13.3 mm²65 A679.56 V (326.71%)0.0 V1120.96 V (538.92%)1177032.2 WDrop/Amp High
4 AWG21.15 mm²85 A427.34 V (205.45%)0.0 V704.9 V (338.9%)740166.8 WDrop/Amp High
3 AWG26.67 mm²100 A338.89 V (162.93%)0.0 V559.01 V (268.75%)586971.4 WDrop/Amp High
2 AWG33.62 mm²115 A268.83 V (129.25%)0.0 V443.45 V (213.2%)465631.4 WDrop/Amp High
1 AWG42.41 mm²130 A213.11 V (102.46%)0.0 V351.54 V (169.01%)369123.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A168.97 V (81.24%)39.0 V278.72 V (134.0%)292662.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A134.04 V (64.44%)74.0 V221.1 V (106.3%)232159.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A106.32 V (51.11%)101.7 V175.38 V (84.32%)184149.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A84.31 V (40.53%)123.7 V139.07 V (66.86%)146031.0 WDrop/Amp High
250 kcmil126.7 mm²255 A71.34 V (34.3%)136.7 V117.67 V (56.57%)123555.9 WDrop/Amp High
300 kcmil152.0 mm²285 A59.46 V (28.59%)148.5 V98.08 V (47.16%)102990.3 WDrop/Amp High
350 kcmil177.3 mm²310 A50.98 V (24.51%)157.0 V84.09 V (40.43%)88294.0 WDrop/Amp High
400 kcmil202.7 mm²335 A44.59 V (21.44%)163.4 V73.55 V (35.36%)77230.0 WDrop/Amp High
500 kcmil253.4 mm²380 A35.67 V (17.15%)172.3 V58.83 V (28.29%)61777.9 WDrop/Amp High
600 kcmil304.0 mm²420 A29.73 V (14.29%)178.3 V49.04 V (23.58%)51495.2 WDrop/Amp High
750 kcmil380.0 mm²475 A23.78 V (11.43%)184.2 V39.23 V (18.86%)41196.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A17.84 V (8.58%)190.2 V29.42 V (14.15%)30895.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 800 feet one-way at 208V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.95V (2.86%) and delivers 202.1V at the load.

What size aluminum wire is required for 1000 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 29.42V (14.15%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.