🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.71%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 0.89V (0.74%)
Voltage at Load End119.1 VLoss: 0.85 V (93.9 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.8 V (11.5%)106.2 V22.76 V (18.97%)1517.8 WDrop/Amp High
12 AWG3.31 mm²20 A8.67 V (7.23%)111.3 V14.3 V (11.92%)953.8 WDrop/Amp High
10 AWG5.26 mm²30 A5.46 V (4.55%)114.5 V9.0 V (7.5%)600.2 WDrop/Amp High
8 AWG8.37 mm²50 A3.43 V (2.86%)116.6 V5.66 V (4.71%)377.2 WDrop/Amp High
6 AWG13.3 mm²65 A2.16 V (1.8%)117.8 V3.56 V (2.97%)237.4 WDrop/Amp High
4 AWG21.15 mm²85 A1.36 V (1.13%)118.6 V2.24 V (1.87%)149.3 WDrop/Amp High
3 AWG26.67 mm²100 A1.08 V (0.9%)118.9 V1.78 V (1.48%)118.4 WDrop/Amp High
2 AWG33.62 mm²115 A0.85 V (0.71%)119.1 V1.41 V (1.17%)93.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.68 V (0.56%)119.3 V1.12 V (0.93%)74.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.54 V (0.45%)119.5 V0.89 V (0.74%)59.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.43 V (0.35%)119.6 V0.7 V (0.59%)46.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.34 V (0.28%)119.7 V0.56 V (0.46%)37.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.27 V (0.22%)119.7 V0.44 V (0.37%)29.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.23 V (0.19%)119.8 V0.37 V (0.31%)24.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.19 V (0.16%)119.8 V0.31 V (0.26%)20.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.16 V (0.13%)119.8 V0.27 V (0.22%)17.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (0.12%)119.9 V0.23 V (0.19%)15.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.09%)119.9 V0.19 V (0.16%)12.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.08%)119.9 V0.16 V (0.13%)10.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.06%)119.9 V0.12 V (0.1%)8.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.05%)119.9 V0.09 V (0.08%)6.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 20 feet one-way at 120V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 0.85V (0.71%) and delivers 119.1V at the load.

What size aluminum wire is required for 110 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 0.89V (0.74%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.