🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 3.27V (2.72%)
Voltage at Load End117.0 VLoss: 2.95 V (324.9 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A120.73 V (100.61%)0.0 V199.15 V (165.96%)13280.6 WDrop/Amp High
12 AWG3.31 mm²20 A75.87 V (63.22%)44.1 V125.15 V (104.29%)8345.5 WDrop/Amp High
10 AWG5.26 mm²30 A47.74 V (39.79%)72.3 V78.75 V (65.63%)5251.7 WDrop/Amp High
8 AWG8.37 mm²50 A30.0 V (25.0%)90.0 V49.49 V (41.24%)3300.3 WDrop/Amp High
6 AWG13.3 mm²65 A18.88 V (15.73%)101.1 V31.15 V (25.95%)2077.0 WDrop/Amp High
4 AWG21.15 mm²85 A11.87 V (9.89%)108.1 V19.59 V (16.32%)1306.1 WDrop/Amp High
3 AWG26.67 mm²100 A9.42 V (7.85%)110.6 V15.53 V (12.94%)1035.8 WDrop/Amp High
2 AWG33.62 mm²115 A7.47 V (6.22%)112.5 V12.32 V (10.27%)821.6 WDrop/Amp High
1 AWG42.41 mm²130 A5.92 V (4.93%)114.1 V9.77 V (8.14%)651.3 W~ ≤5%
1/0 AWG53.49 mm²150 A4.69 V (3.91%)115.3 V7.74 V (6.45%)516.4 W~ ≤5%
2/0 AWG67.43 mm²175 A3.72 V (3.1%)116.3 V6.14 V (5.12%)409.7 W~ ≤5%
3/0 AWG85.01 mm²200 A2.95 V (2.46%)117.0 V4.87 V (4.06%)324.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.34 V (1.95%)117.7 V3.86 V (3.22%)257.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.98 V (1.65%)118.0 V3.27 V (2.72%)218.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.65 V (1.38%)118.3 V2.73 V (2.27%)181.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.42 V (1.18%)118.6 V2.34 V (1.95%)155.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.24 V (1.03%)118.8 V2.04 V (1.7%)136.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.99 V (0.83%)119.0 V1.63 V (1.36%)109.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.83 V (0.69%)119.2 V1.36 V (1.14%)90.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.66 V (0.55%)119.3 V1.09 V (0.91%)72.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.41%)119.5 V0.82 V (0.68%)54.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 175 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 2.95V (2.46%) and delivers 117.0V at the load.

What size aluminum wire is required for 110 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 3.27V (2.72%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.